Hydronic piping, Installation & operation manual – Lochinvar 81 - 286 User Manual

Page 42

background image

42

Installation & Operation Manual

DOMESTIC
HOT WATER
CIRCULATOR

ANTI-SCALD

MIXING VALVE

COLD
WATER
IN

AIR SEPARATOR

BALL VALVE

(TYPICAL)

DRAIN POINT

(TYPICAL)

MAKE

UP

WATER

HOT

WATER

OUT

BOILER
CIRCULATOR

BACKFLOW

PREVENTER

PRESSURE
REDUCING VALVE

PRESSURE

GAUGE

EXPANSION

TANK

MIXING VALVES

(TYPICAL)

FLOW CHECK
VALVE

SYSTEM

SUPPLY
SENSOR

MAY SUBSTITUTE LOW LOSS HEADER

TEMPERATURE

LOOP #1

TEMPERATURE

LOOP #2

TEMPERATURE

LOOP #3

BOILER

INDIRECT

DHW TANK

TEMPERATURE /

PRESSURE

GAUGE

UNION

(TYPICAL)

DRAIN

Y-STRAINER
(RECOMMENDED)

NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART

BOILER

Figure 6-7 Multiple Boilers - Multiple Temperatures

Model

Number of Units

2

3

4

5

6

7

8

Required Pipe Sizes

81

1-1/4" 1-1/2"

2"

2"

2-1/2" 2-1/2" 2-1/2"

106

1-1/2"

2"

2"

2-1/2" 2-1/2" 2-1/2"

3"

151

2"

2"

2-1/2" 2-1/2"

3"

3"

3-1/2"

211

2"

2-1/2"

3"

3"

3-1/2"

4"

4"

286

2-1/2" 2-1/2"

3"

3-1/2" 3-1/2"

4"

5"

Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.

NOTICE

6

Hydronic piping

CAUTION

Mixing valves are required for the protection of low temperature loops.