beautypg.com

General, Venting, Install vent and combustion air piping – Lochinvar 81 - 286 User Manual

Page 16: Requirements for installation in canada

background image

16

Installation & Operation Manual

3

General

venting

PVC/CPVC vent piping materials

Use only the materials listed in Table
3A for vent pipe, and fittings. Failure to
comply could result in severe personal
injury, death, or substantial property
damage.

Installation must comply with local
requirements and with the National
Fuel Gas Code, ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.

Install vent and combustion air piping

ƽ DANGER

The Knight boiler must be vented and
supplied with combustion and ventilation
air as described in this section. Ensure the
vent and air piping and the combustion
air supply comply with these instructions
regarding vent system, air system, and
combustion air quality. See also Section 1
of this manual.

Inspect finished vent and air piping
thoroughly to ensure all are airtight and
comply with the instructions provided and
with all requirements of applicable codes.

Failure to provide a properly installed vent
and air system will cause severe personal
injury or death.

All PVC vent pipes must be glued, properly
supported, and the exhaust must be
pitched a minimum of a 1/4 inch per foot
back to the boiler (to allow drainage of
condensate).

ƽ WARNING

NOTICE

ƽ WARNING

ƽ WARNING

For closet and alcove installations, CPVC
or stainless steel material MUST BE used in
a closet/alcove structure. Failure to follow
this warning could result in fire, personal
injury, or death.

NOTICE

Requirements for installation in
Canada

1. Installations must be made with a vent pipe system

certified to ULC-S636.

IPEX is an approved vent manufacturer in Canada

supplying vent material listed to ULC-S636.

2. The first three (3) feet of plastic vent pipe from the

appliance flue outlet must be readily accessible for visual

inspection.

3. The components of the certified vent system must not be

interchanged with other vent systems or unlisted

pipe/fittings. For concentric vent installations, the inner

vent tube must be replaced with field supplied certified vent

material to comply with this requirement.

4. The 3" Concentric Vent Kit available from Lochinvar (see

Section 4 – Sidewall Termination – Optional Concentric

Vent) and the 3" Concentric Vent Kit available from IPEX

are both approved for use on the Knight boiler. Both

kits are listed to the ULC-S636 standard for use in Canada.

This appliance requires a special venting
system. The vent connection to the
appliance must be made with the starter
CPVC pipe section provided with the
appliance if PVC/CPVC vent is to be used.
For stainless steel venting use an adapter
from Table 3B (page 19) that corresponds
with the intended vent manufacturer to
be used and discard the CPVC starter
piece. The field provided vent fittings must
be cemented to the CPVC pipe section
using an “All Purpose Cement” suitable for
PVC and CPVC pipe. Use only the vent
materials, primer, and cement specified in
this manual to make the vent connections.
Failure to follow this warning could result
in fire, personal injury, or death.

Installing vent and air piping

Improper installation of PVC or CPVC
systems may result in injury or death.

ƽ CAUTION

Use only cleaners, primers, and solvents that
are approved for the materials which are
joined together.

NOTICE

1. Work from the boiler to vent or air termination. Do not

exceed the lengths given in this manual for the air or vent

piping.

2. Cut pipe to the required lengths and deburr the inside and

outside of the pipe ends.

3. Chamfer outside of each pipe end to ensure even cement

distribution when joining.

4. Clean all pipe ends and fittings using a clean dry rag.

(Moisture will retard curing and dirt or grease will prevent

adhesion.)

5. Dry fit vent or air piping to ensure proper fit up before

assembling any joint. The pipe should go a third to

two-thirds into the fitting to ensure proper sealing after

cement is applied.

ƽ WARNING

Insulation should not be used on PVC
or CPVC venting materials. The use of
insulation will cause increased vent wall
temperatures, which could result in vent
pipe failure.