beautypg.com

Battery cabinet specifications, Attery, Abinet – Liebert 208V User Manual

Page 35: Pecifications

background image

31

BATTERY CABINET SPECIFICATIONS

Model Number

GXT2-72VBATT

Used w/ UPS Model

GXT2-2700RT208

DIMENSIONS in (mm)

Unit - W x D x H in. (mm)

3.5 x 24.2 x 17 (87 x 618 x 430)

Shipping - W x D x H in. (mm) 10.5 x 27.2 x 23 (268 x 692 x 585)

WEIGHT lbs (kg)

Unit: lbs (kg)

93.6 (42.5)

Shipping: lbs (kg)

102.5 (46.5)

BATTERY PARAMETERS

Type

Valve-regulated, nonspillable, flame retardant, lead acid

Qty x V x Rating

2 x 6 x 12V x 9.0 AH

Battery Mfg/Part #

Panasonic/UP-VW1245P1
Yuasa/REW 45-12 FR

Back-Up Time

See Battery Run Times charts

ENVIRONMENTAL

Operating Temp

+32°F to +104°F (0°C to +40°C)

Storage Temp

+5°F to +122°F (-15°C to +50°C)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 10,000 ft. (3000 m) at 104°F (40°C)
without derating

Storage Elevation

50,000 ft. (15,000 m) maximum

AGENCY

Safety

UL 1778, c-UL Listed (Suitable for computer room
applications)

RFI/EMI

FCC Part 15, Subpart B, Class A

Transportation

ISTA Procedure 1A