Pins 5 & 6 - any-mode shutdown, Auto-enable output, Pin 6 logic – Liebert 208V User Manual

Page 24: Auto-enable output pin 6 logic, Warning

background image

20

3. A battery shutdown signal on Pin 4 will NOT cause an immediate

shutdown. A shutdown signal will start a 2-minute shutdown timer.
The timer cannot be stopped. After 2 minutes, the UPS will shut
down.

4. If the utility returns during the 2-minute timer countdown, the shut-

down timer will continue until the end of 2 minutes and the UPS will
turn OFF. The UPS must remain OFF for at least 10 seconds even if
AC input power returns before the UPS turns OFF. This serves to
reset and restart the server.

Whether the UPS turns back ON when power is restored depends on the
auto-restart setting: enabled or disabled.
If the auto-restart is disabled, the UPS will not restart after performing the
2-minute shutdown delay.

P

INS

5 & 6 - A

NY

-M

ODE

S

HUTDOWN

1. Pin 6 of the 9-pin communication connector is used for “Any-Mode

Shutdown” of the UPS output. This control input may be used in spe-
cial applications to disable the UPS output power—both Inverter and
Bypass.

2. The Options tab allows the behavior of the Any-Mode Shutdown fea-

ture to be modified. When the program opens, or the REFRESH but-
ton is pressed, the UPS setting is read by the configuration program
and displayed.

Auto-Enable Output

Pin 6 Logic

If version 1.6 (or later) is used with an earlier GXT 2U model (with an ear-
lier UPS firmware version), the Any-Mode Shutdown features cannot be
changed.

!

WARNING

Note that when this option is selected and the UPS output

is disabled using Pin 6, the UPS output can turn on

automatically and without warning if the Pin 6 connection

is changed.

!

WARNING

DO NOT CHANGE THIS OPTION from the factory default

setting unless you are ready to install a normally-closed

connection between Pins 5 & 6. This connection must be

maintained to use the UPS or to use the configuration

program again, including the ability to change the UPS

setting back to the default setting using the configuration

program via a serial communication link.