Troubleshooting guide (continued) – Liebert 208V User Manual

Page 32

background image

28

Fault and Bypass

indicator LEDs

and diagnostic

LED C and E are

illuminated.

UPS shutdown due to a

command from the

communications port(s).

Your UPS has received a

signal or command from the

attached computer. If this

was inadvertent, ensure the

communication cable used

is correct for your system.

For assistance, contact your

local dealer, Liebert

representative or the Liebert

Worldwide Support Group.

AC LED is

flashing.

UPS detected a line-to-

neutral reversal or a loss of

proper grounding;

continuous horn and UPS

will not start.This is active

only when power is first

applied to the input. Once

the UPS is running, the AC

LED will not start flashing,

even if the input wiring is

changed.

Contact a qualified

electrician to verify site

wiring.

Battery LED is

flashing.

Battery source is not

available; continuous horn.

Check battery connections,

completely power down and

restart UPS.

NOTE: If the battery circuit

opens while the UPS is

running, it will be detected

when the next battery test is

performed.

Bypass LED is

flashing.

Bypass voltage is present,

but is disabled for use

because the voltage or

frequency is outside

acceptable limits.

The AC input powers the

PFC input and serves as the

bypass source. If the AC is

present but the voltage or

frequency exceeds the

acceptable range for safe

operation with a load, the

bypass will be disabled and

this LED will flash, indicating

that the bypass is

unavailable.

Troubleshooting Guide (Continued)

Problem

Cause

Solution