Installation Guide for Dimming and Switching Panels 11
Ratings
Number
of
Modules
Feed
Type
Max.
Feed
Feed-Through Panels
(all voltages)
1
2
3
4
5
6
7
8
9
1Ø, 2W
#14-#10 AWG
(1.5-4.0 mm
2
)
120 V
: 20 A
230 V
: 13 A or 16 A
220-240 V
: 16 A
LP/LCP/CCP Panels
Panels with Breaker
(120 V
only)
Number
of
Modules
Feed
Type
1
2
3
1Ø, 2W
1Ø, 3W
3Ø, 4W
#14-#10 AWG
(1.5-4.0 mm
2
)
Panels with Main Lugs
(120 V
only)
Number
of
Modules
Feed
Type
Maximum
Feed
4
5
6
7
8
9
1Ø, 3W or 3Ø, 4W
#14-#2/0 AWG
(25-70 mm
2
)
175 A
Panels with Breaker
(220-240 V
and 230 V
only)
Number
of
Modules
Feed
Type
1
2
3
1Ø, 2W
1Ø, 2W
3Ø, 4W
#14-#12 AWG
(1.5-4.0 mm
2
)
Panels with Isolation Switch
(220-240 V
and 230 V
only)
Number
of
Modules
Feed
Type
Maximum Feed
230 V
220-240 V
4
5
6
7
8
3Ø, 4W
#14-#2/0 AWG
(25-70 mm
2
)
125 A
125 A