Troubleshooting – Lochinvar KNIGHT 399 User Manual

Page 39

background image

3

Troubleshooting

(continued)

Service Manual

39

Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

Service Blk

While the unit is in Service Mode, the outlet
temperature has exceeded 185°F.

• Establish a heating load to remove the heat from the

boiler loop.

• Verify that the system is full of water and that all air

has been properly purged from the system.

• Verify that the boiler is piped properly into the heating

system. Refer to Section 6 - Hydronic Piping of the
Knight XL Installation and Operation Manual for the
proper piping methods for the Knight XL boiler.

• Check voltage to the boiler pump motor on a call for

heat. If voltage is not present, check the wiring back
to the pump relay. Replace the pump relay if
necessary.

• If 120 VAC is present on a call for heat and the boiler

pump is not operating, replace the pump.

• Verify that the boiler pump is set to the proper speed

or that the boiler pump is the proper size. Reference
Section 6 - Hydronic Piping of the Knight
XL Installation and Operation Manual for boiler
pump specifications.

Low 24 VAC

120 VAC input to the main control board has
dropped below 80 VAC.

• Check 120 VAC supply to the transformer.

• Check wiring connections at the low voltage terminal

strip.

• Check the wire size/length to remote devices.

• Replace the transformer.

Watch Dog Error

The main control board has detected an
internal fault.

• Replace the main control board.

Write EEProm

The main control board has detected an
internal fault.

• Replace the main control board.

CRC Parameters

The main control board has detected an
internal fault.

• Replace the main control board.

No Error Stored

The main control board has detected an
internal fault.

• Press the ENTER/RESET button on the SMART

SYSTEM display panel.