Warning, Caution – Lennox International Inc. MERIT PLUS MPB3530CNM-B User Manual
Page 13

13
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MERIT PLUS
®
B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS
Operate the actuator through several 
cycles including the closed position. 
Ensuring proper operation and freedom of 
movement. Return the actuator arm to the 
closed position.
Note: Do not terminate an outside air kit in the 
attic space under any circumstances. 
After completing the installation of the 
optional outside air vent system the outside 
air control lever must be put in service and 
tested to ensure proper operation before 
completing any enclosure around the fi rebox. 
Failure to do so may result in extensive and 
costly rework. Before the operation of the 
vent system can be tested, the lever securing 
screw must be removed (see Figure 20).
The hand operated outside air control lever 
is located on the left side of the fi replace 
opening (see Figure 20).
STEP 7. INSTALLING OUTSIDE AIR KIT
Optional outside make-up air kits, Model 
FOAK-4 or FAOK-4LD (see Figure 21 on Page 
14), may be used with these appliances. 
Refer to the installation instructions packaged 
with the air kits for specifi c installation 
information. If used, the outside air kit must 
be installed before the fi replace is framed and 
enclosed in the fi nished wall.
Outside air drawn into the fi replace supplies 
air to the fi re for combustion. Only one 
outside air duct is necessary, if installed. See 
Figure 3 on Page 5 for the location of the 
unit's outside air inlet.
If additional length of duct is necessary, 
purchase locally available U.L. Class 0
or Class 1 metallic ducting. The duct may 
extend up to 50' (15.24 m) in any direction.
Note: When installing the air duct vertically, DO 
NOT terminate the duct closer than 3' below 
the chimney top.
Outside supplemental combustion air ducting 
may be run upwards or vertically through 
framing and ceiling joists, with the hood 
installed through an outside wall and 3' (1 m)
below the termination. Ducting may also 
be run downward through fl oor joists and 
under the home to a ventilated crawlspace 
not considered part of the living area of the 
home.
Outside Air Control Lever
Outside Air Control Lever
Securing screw
Air Shutter in Closed Position
Outside Air Control Lever
Outside Air Control Lever
Securing Screw Removed
Air Shutter in Open Position
Figure 20: Outside Air Control Lever
WARNING
DO NOT operate the outside 
air control lever with a fi re in 
the fi rebox unless a complete 
outside combustion air vent 
system has been installed with 
the appliance.
CAUTION
Never locate inlet where it can be 
blocked by shrubs, snow drifts, 
etc. Never locate inlet in garage 
or any area where there is another 
fuel burning appliance or products 
emitting combustible gases such 
as paint, gasoline, etc. In cold 
climates, it is recommended the 
outside air duct be insulated.
To open the outside air shutter, open the 
bottom control access panel, reach into the 
control compartment, and pull the outside 
air control lever all the way out. The outside 
air shutter should be fully open when the 
fi replace is in use and completely closed 
when the fi replace is not being used. Closing 
it when not in use will prevent outside cold 
air from entering the dwelling.
Figure 18: Gas Connection
Gas
Stub
1/2" x 3/8" Flare
Shut-Off Valve
3/8" Flex Tubing
3/8" NPT x 3/8"
Flare Fitting
3/8" Nipple
3/8" Union
3/8" Close Nipple
3/8" Shut-Off Valve
1/2" x 3/8"
Reducer
Gas
Valve
Optional Gas Flex Line Connector
Piezo
(Optional) Burner
ON/OFF Switch
Main Gas
Shut-Off Valve
Gas Valve
B-Vent Units Have
A Single Door Latch
Figure 19: Millivolt Gas Valve—Lower Control Compartment
