Field wiring, Installation must comply with, Low voltage connections – Lochinvar KNIGHT 51 User Manual

Page 50: Line voltage connections

background image

8

Field wiring

ELECTRICAL SHOCK HAZARD – For
your safety, turn off electrical power
supply before making any electrical
connections to avoid possible electric
shock hazard. Failure to do so can cause
severe personal injury or death.

Wiring must be N.E.C. Class 1.

If original wiring as supplied with boiler
must be replaced, use only type 105°C
wire or equivalent.

Boiler must be electrically grounded as
required by National Electrical Code
ANSI/NFPA 70 – latest edition.

Installation must comply with:

1. National Electrical Code and any other national, state,

provincial, or local codes, or regulations.

2. In Canada, CSA C22.1 Canadian Electrical Code Part 1,

and any local codes.

3. Wire the boiler pump as shown in FIG. 8-2.

4. When connecting a domestic hot water (DHW) pump,

connect the wiring to the line voltage terminal strip as
shown in FIG. 8-2.

5. To activate a system pump, wire as shown in FIG. 8-2. If the

motor is larger than 1/8 hp or 1.8 amps, you must isolate
with a relay.

Figure 8-2 Line Voltage Field Wiring Connections

Label all wires prior to disconnection
when servicing controls. Wiring errors
can cause improper and dangerous
operation.

ƽ WARNING

NOTICE

ƽ CAUTION

REMOVE BEZEL

Figure 8-1 Remove Bezel

Low voltage connections

1.

Route all low voltage wires through the knockouts in the
bottom front right side, just under the control panel, as
shown in FIG. 8-3.

2.

Connect low voltage wiring to low voltage connection board
as shown in FIG. 8-4 on page 53 of this manual and the
boiler wiring diagram.

LOW VOLTAGE
WIRING KNOCKOUTS

LOW VOLTAGE
CONNECTION BOARD

LINE VOLTAGE
WIRING KNOCKOUTS

LINE VOLTAGE
JUNCTION BOX

Figure 8-3 Routing Field Wiring

Line voltage connections

1. Remove bezel as shown in FIG. 8-1.

2. Connect 120 vac power wiring to the line voltage terminal

strip in the junction box, as shown in FIG. 8-2.

2. Provide and install a fused disconnect or service switch

(15 amp recommended) as required by the code (see
FIG. 8-2).

50

Installation & Operation Manual