Hydronic piping, 20°f temperature rise applications, 25°f temperature rise applications – Lochinvar KNIGHT 51 User Manual
Page 36: 35°f temperature rise applications
Installation & Operation Manual
36
6
Hydronic piping
6
Figure 6-2 Pressure Drop vs. Flow - Models 50 - 210
20°F Temperature Rise Applications
Model
GPM
FT/HD
Minimum Pipe
Size
Pump
Grundfos
TACO
B & G
Armstrong
51
5.1
11
1"
UPS26-99F
0011
NRF-36
E7
81
7.5
24
1"
UPS26-99F
0011
NRF-36
E7
106
9.8
27
1"
UPS26-99F
0013
NRF-36
E11
151
14.0
20
1"
UPS26-99F
0011
NRF-36
E7
211
19.6
29
1"
UPS32-160
1400-50
PL-55
E9
Table 6A Circulator Recommendations for Temperature Rise Applications_20°, 25°, and 35°
25°F Temperature Rise Applications
Model
GPM
FT/HD
Minimum Pipe
Size
Pump
Grundfos
TACO
B & G
Armstrong
51
4.1
7.3
1"
UPS15-58FC
0014
NRF-36
E7
81
5.9
15.0
1"
UPS15-58FC
0014
NRF-36
E7
106
7.7
17.5
1"
UPS26-99F
0014
NRF-36
E7
151
11.0
12.8
1"
UPS26-99F
0014
NRF-36
E7
211
15.5
19.0
1"
UPS26-99F
0013
NRF-36
E7
35°F Temperature Rise Applications
Model
GPM
FT/HD
Minimum Pipe
Size
Pump
Grundfos
TACO
B & G
Armstrong
51
2.9
4.1
1"
UPS15-58FC
007
NRF-22
Astro-30
81
4.2
7.3
1"
UPS15-58FC
007
NRF-22
Astro-30
106
5.5
9.8
1"
UPS15-58FC
007
NRF-22
Astro-30
151
7.9
10
1"
UPS15-58FC
008/0010
NRF-36
Astro-30
211
11.0
10.1
1"
UPS15-58FC
0010
NRF-36
Astro-50
Pumps listed in bold type are provided by the factory as the boiler circulation pump on standard altitude
models.
NOTICE
Pumps listed in italicized type are provided by the factory as the boiler circulation pump on high altitude
models.
NOTICE
The temperature rise provided by a pump/model combination will decrease by 3% per 1000 feet of elevation.
NOTICE