Hydronic piping

6

Figure 6-2 Pressure Drop vs. Flow - Models 50 - 210

20°F Temperature Rise Applications

Model

GPM

FT/HD

Minimum Pipe

Size

Pump

Grundfos

TACO

B & G

Armstrong

51

5.1

11

1"

UPS26-99F

0011

NRF-36

E7

81

7.5

24

1"

UPS26-99F

0011

NRF-36

E7

106

9.8

27

1"

UPS26-99F

0013

NRF-36

E11

151

14.0

20

1"

UPS26-99F

0011

NRF-36

E7

211

19.6

29

1"

UPS32-160

1400-50

PL-55

E9

Table 6A Circulator Recommendations for Temperature Rise Applications_20°, 25°, and 35°

25°F Temperature Rise Applications

Model

GPM

FT/HD

Minimum Pipe

Size

Pump

Grundfos

TACO

B & G

Armstrong

51

4.1

7.3

1"

UPS15-58FC

0014

NRF-36

E7

81

5.9

15.0

1"

UPS15-58FC

0014

NRF-36

E7

106

7.7

17.5

1"

UPS26-99F

0014

NRF-36

E7

151

11.0

12.8

1"

UPS26-99F

0014

NRF-36

E7

211

15.5

19.0

1"

UPS26-99F

0013

NRF-36

E7

35°F Temperature Rise Applications

Model

GPM

FT/HD

Minimum Pipe

Size

Pump

Grundfos

TACO

B & G

Armstrong

51

2.9

4.1

1"

UPS15-58FC

007

NRF-22

Astro-30

81

4.2

7.3

1"

UPS15-58FC

007

NRF-22

Astro-30

106

5.5

9.8

1"

UPS15-58FC

007

NRF-22

Astro-30

151

7.9

10

1"

UPS15-58FC

008/0010

NRF-36

Astro-30

211

11.0

10.1

1"

UPS15-58FC

0010

NRF-36

Astro-50

Pumps listed in bold type are provided by the factory as the boiler circulation pump on standard altitude
models.

NOTICE

Pumps listed in italicized type are provided by the factory as the boiler circulation pump on high altitude
models.

NOTICE

The temperature rise provided by a pump/model combination will decrease by 3% per 1000 feet of elevation.

NOTICE