Table 5
Series 600T Multi-Module Systems, 500-750 kVA - 600 Volt Input
UPS
Rating
AC
Output
Voltage
Options
Rectifier
AC
Input
Current
Inverter
or
Bypass
AC Output
Current
Required
Battery
Discon-
nect
Rating
Maximum
Battery
Current
at End of
Discharge
Maximum
Heat Dis-
sipation
BTU/hr.
Dimen-
sions
Inches
Approx.
Weight
Lb.
Floor
Loading
Lb./
Sq.ft.
kVA
kW
Input
Filter
Input
Xfmr Nom
Max Nom
Max
Amps
Amps
Full
Load
(WxDxH)
(Un-
packed)
(Concen-
trated
Loading)
500
400
600
NO
NO
484
605
481
601
1,000
1,079
94,900
72x39x79
6,110
313
500
400
600
YES
NO
449
561
481
601
1,000
1,079
99,600
72x39x79
6,310
324
500
400
600
NO
YES
490
612
481
601
1,000
1,079
110,700
96x39x79
8,710
355
500
400
600
YES
YES
454
567
481
601
1,000
1,079
115,500
96x39x79
8,910
343
500
450
600
NO
NO
545
681
481
601
1,200
1,214
106,750
72x39x79
6,130
314
500
450
600
YES
NO
505
631
481
601
1,200
1,214
112,050
72x39x79
6,330
325
500
450
600
NO
YES
551
688
481
601
1,200
1,214
124,550
96x39x79
9,030
347
500
450
600
YES
YES
510
638
481
601
1,200
1,214
129,950
96x39x79
9,230
355
625
500
600
NO
NO
602
753
601
752
1,400
1,349
108,950
108x39x79
7,805
300
625
500
600
YES
NO
559
699
601
752
1,400
1,349
118,650
108x39x79
8,025
309
625
500
600
NO
YES
609
761
601
752
1,400
1,349
128,450
120x39x79
10,485
323
625
500
600
YES
YES
554
705
601
752
1,400
1,349
134,400
120x39x79
10,705
329
750
600
600
NO
NO
723
903
722
902
1,600
1,619
130,700
108x39x79
8,405
323
750
600
600
YES
NO
671
839
722
902
1,600
1,619
142,350
108x39x79
8,625
332
750
600
600
NO
YES
730
913
722
902
1,600
1,619
154,150
120x39x79
11,485
353
750
600
600
YES
YES
677
846
722
902
1,600
1,619
161,250
120x39x79
11,705
360
750
675
600
NO
YES
822
1027
722
902
1,600
1,822
173,400
120x39x79
11,785
363
750
675
600
YES
YES
762
952
722
902
1,600
1,822
181,400
120x39x79
12,005
369
Applicable
Notes:
—
13
—
1,4,5,7,8,
9,11,12
2,3,5,7,8,
9,11,12
6
6,8,9,
11,12
—
14
14
—
For explanation of notes, see referenced numbers in 12.1 - Notes