0 wiring inspection, Iring, Nspection – Liebert 600TTM User Manual
Page 33: Table 1 power wiring terminals - factory supplied, Table 2 torque specifications, Table 1, Table 2

Wiring Inspection
27
10.0 W
IRING
I
NSPECTION
1.
Verify all power connections are tight.
2.
Verify all control wire terminations are tight.
3.
Verify all power wires and connections have proper spacing between exposed surfaces, phase-
to-phase and phase-to-ground.
4.
Verify that all control wires are run in individual, separate, steel conduit.
Table 1
Power Wiring Terminals - Factory Supplied
UPS Module Rating
Connection Type
500 kVA, 6-Pulse Rectifier
All power connections are top or bottom cable entry to busbars on the right
side of module.
500 kVA, 12-Pulse
Rectifier
Busbars for DC input, AC output, Neutral and Ground are provided on the
right side of module, with top or bottom cable entry. Rectifier input is top entry
directly to lugs on top of input circuit breaker.
625-750 kVA, standard
models with standard input
Busbars for AC output, Neutral and Ground are provided on the right side of
module, with top or bottom cable entry. Rectifier input is top entry directly to
lugs on top of input circuit breaker. DC input is top entry to bus bars.
750 kVA/675 kW and other
modules with optional
input busbar kit
Busbars for AC output, Neutral and Ground are provided on the right side of
module, with top or bottom cable entry. Rectifier input and DC input are top
entry to bus bars.
Use 75°C copper wire. Select wire size based on the ampacities in Table 310-16 (see Table 3 of this
manual) and associated notes of the National Electrical Code (NFPA 70).
Use commercially available solderless lugs for the wire size required for your application. Connect wire to
the lug using tool and procedure specified by the lug manufacturer.
Table 2
Torque Specifications
Nut and Bolt Combinations
Bolt Shaft Size
Grade 2
Standard
Electrical Connections
with Belleville Washers
Lb-in
N-m
Lb-in
N-m
1/4
53
6.0
46
5.2
5/16
107
12
60
6.8
3/8
192
22
95
11
1/2
428
48
256
29
Circuit Breakers With Compression Lugs (For Power Wiring)
Cable Size or Range
Lb-in
N-m
#6 - #4
100
11
#3 - #1
125
14
1/0 - 2/0
150
17
3/0 - 200 MCM
200
23
250 - 400 MCM
250
28
500 - 700 MCM
300
34
Terminal Block Compression Lugs (For Control Wiring)
AWG Wire Size or Range
Lb-in
N-m
#22 - #14
3.5 to 5.3
0.4 to 0.6
Use the values in this table unless the equipment is labeled with a
different torque value.