APPENDIX
WTC 600 LP / MP
Service Handbook 08.2004
3
Operational Scope
3.1
Operating settings
The control system allows to preselect the following operating settings (realization see item 4).
The resulting control behaviours are described in the chapter Operating Conditions. The
standard values (setting after parameter reset) are marked by * in the appropriate field.
ps LIM high
function:
Preselect if unit is to be switched off if
LIM is exceeded or if a failure
message is sufficient
right of access:
user/technician
possible setting:
* switch off do
not switch off
ps acknowledgment
function:
Prelesect if acknowledgment of
failures is possible in the normal level
(=without password)
or only in the user/technician level
(=with password).
right of access:
technician
possible setting:
* without password
with password
ps concentrate mode
function:
Preselect if PRODUCTION has to be
followed by CONCENTRATE FLUSH
(with pump) or CONCENTRATE
DISPLACEMENT (without pump).
right of access:
technician
possible setting:
* flush
displacement
ps tank type
function:
Prelesect if tank is equipped with an
overflow or not. Should the tank have
an overflow, the produced water
continues to flow into the tank during
CONCENTRATE DISPLACEMENT/
FLUSH and DISCONTINUOUS
RINSE.
right of access:
technician
possible setting:
* with
without overflow