beautypg.com

Specifications – Schneider Electric 170AMM11030 User Manual

Page 5

background image

31005009 01 November 2003

5

Specifications

Overview

This section contains specifications for the 170AMM11030 Momentum I/O base.

General
Specifications

The following table contains general specifications for the I/O base. Each discrete
output is protected against short-circuiting and overload.

External Power Requirement

Normal Operating Voltage Range

16 to 42 VDC

Absolute Minimum Voltage

12 VDC

Absolute Maximum Voltage

45 VDC

Electrical

Module Current

400 mA at 24 VDC

EMC for Industrial Environment

Immunity

IEC 1131-2

Surge on auxiliary power supply 500 V

Emissions

EN 50081-2

ENV 50140

10 V/M

Agency Approvals

UL, CSA, CE, FM Class 1, Div. 2 (pending)

Isolation

Discrete I/O point to discrete I/O point

None

Field to ground

500 VAC

Field to communication adapter

500 VAC

Analog output channel to channel

700 VDC

Environmental

Storage Temperature

-40 to 85

° C

Operating Temperature

0 to 60

° C

Humidity Operating

95% RH @ 60

° C

Humidity Non-Operating

95% RH @ 60

° C

Vibration Operating

10 - 57 HZ 0.075 MMDA

57 - 150 HZ 1 G

Shock Non-Operating

15 G, 11 MS, 3 shocks/axis

Free Fall (Unpackaged)

0.1 meter