Wiring ( continued )

24VDC

24VDC

Brown : 24VDC (for solenoid valves/output)

White : 0V (for solenoid valves/output)

Grey : Earth

Blue : 24VDC (for input and control)

Black : 0V (for input and control)

Cable Part No. : EX500-AP -S

24VDC

Brown : 24VDC (for solenoid valves/output)

White : 0V (for solenoid valves/output)

Grey : Earth

Blue : 24VDC (for input and control)

Black : 0V (for input and control)

Cable Part No. : EX500-AP -S

Power supply

connector

Power supply

connector

1

3

4

5

2

1

3

4

5

2

Display/Setting

Connecting one or two power supplies to SI Unit.

Both single power supply and two power supply systems can be adopted, however, the
wiring shall be made separately (for solenoid valves/output and for input and control) for
either system.

A. Two power supplies

B. Single power supply

Settings for display

Display

Contents

SOL

OFF

The power supply for solenoids is insufficient

Green light ON

The power supply for solenoids is normal

PWR

OFF

The power supply for input and control is insufficient

Green light ON

The power supply for input and control is normal

MS

OFF

The power supply for control is OFF

Green light ON

Operating normally

Green flashing

Setting error (Device has not been configured)

Red flashing

Recoverable internal error

Red light ON

Unrecoverable internal error

NS

OFF

The power supply for control is OFF or IP address not set

Green flashing

EtherNet/IP-level communication not established

Green light ON

Multiple EtherNet/IP-level communications established

Red flashing

Multiple EtherNet/IP-level communications time out

Red light ON

IP address duplicated