DHW heating from the primary circuit
(Anl 4):
The control valve opens depending on the
DHW temperature from its closed position.
Stop storage tank charging
The controller stops charging the storage tank when the water temperature in the storage tank
measured at sensor SF1 reaches the value T =
DHW heating ON + Hysteresis. In systems with
two storage tank sensors, the controller stops charging the storage tank when the water temper-
ature in the storage tank measured at sensor SF2 reaches the value
DHW heating OFF. In sys-
tems with storage tank thermostat, the
Hysteresis of the thermostat determines when the storage
tank charging is finished.
When a high flow temperature is required by the system, the storage tank charging pump is im-
mediately switched off. If no heating is taking place or if the flow temperature demand in the
system is lower, the
End charging process parameter applies for switching off the storage tank
charging pump.
The storage tank charging pump is switched off at the latest after two transit time periods of the
control valve (2 x T
Y
).
Functions
WE
Configuration
Storage sensor SF1
ON
FB14
Storage sensor SF2
OFF
FB15
Return flow sensor RüF1
ON
FB20
Parameters
WE
Range of values
DHW heating ON
45 °C
20 to 90 °C
DHW heating OFF
50 °C
20 to 90 °C
Hysteresis
5 °C
0 to 30 °C
Charging temperature
55 °C
20 to 90 °C
Stop charging
53 °C
20 to 90 °C
DHW temperature
55 °C
20 to 90 °C
50
EB 5476 EN
Functions of the DHW circuit