Page 42: 2 4-point characteristic

5.1.2 4-point characteristic
The 4-point characteristic allows you to define your own heating characteristic.
It is defined by 4 points for the
Outdoor temperature, the Flow temperature and the Return flow
temperature. The Set-back difference at points 2 and 3 indicates how much the flow temperature
is reduced outside the times-of-use. The
Max. flow temperature and Min. flow temperature pa-
rameters mark the upper and lower limits of the flow temperature.
Function
WE
Configuration
Characteristic
OFF
FB19 = ON
Parameters
WE
WE*
Range of values
Outdoor temperature, point 1
Outdoor temperature, point 2
Outdoor temperature, point 3
Outdoor temperature, point 4
–15 °C
–5 °C
5 °C
15 °C
–15 °C
–5 °C
5 °C
15 °C
–30 to 20 °C
Flow temperature, point 1
Flow temperature, point 2
Flow temperature, point 3
Flow temperature, point 4
70 °C
55 °C
40 °C
25 °C
50 °C
40 °C
35 °C
20 °C
20 to 130 °C
Return flow temperature, point 1
Return flow temperature, point 2
Return flow temperature, point 3
Return flow temperature, point 4
65 °C
50 °C
35 °C
20 °C
–
–
–
–
20 to 90 °C
Set-back difference, points 2, 3
20 °C
5 °C
0 to 50 °C
Max. flow temperature
90 °C
50 °C
20 to 130 °C
42
EB 5476 EN
Functions of the heating circuit
Fig. 3 · 4-point characteristic
P1 to P4
Points 1 to 4
t
VL
Flow temperature
t
A
Outdoor temperature
... min
Minimum flow temperature
... max
Maximum flow temperature
-----
Set-back characteristic