Sample sequencer, Troubleshooting – SentrySafe SPD 5.5.5 User Manual

Page 54

background image

Sample Sequencer

Troubleshooting

TROUBLESHOOTING


Troubleshooting Guide

Symptom Possible

Problem(s)

Remedy

Display doesn't light

Power



Board connection




Fuse on I/O board

1. Verify power supply outputs 6-9 VDC.
2. Verify polarity is connected correctly to I/O

board.


1. Verify I/O board is snugly connected into I/O

board.

2. Verify I/O board component-side is on right

side from rear view.


1. Remove F1 (3A) on the I/O board and test

for continuity. Replace if defective.

Incorrect ANALOG mA

Analyzer signal


Polarity

1. Verify the input signal from analyzer is 0-20

mA.


2. Verify the analog signal polarity is correctly

connected to the I/O board terminals (+) and
(-) on J4.

Incorrect valve operates

Wiring

1. Verify the interconnected cable (8 conductor)

is correctly connected from the I/O board
terminals and the valve relay board.

Valves don't operate

Valve power



Fuse

1. Verify power was brought to the valve relay

board J1 terminals labeled (+) and (-).

Danger:

Disconnect power before checking

this!

1. Check F1 fuse on the valve relay board.

Replace with 1A fuse if defective.