3 Operating the SAMMS-LV Device

F4 - Full-Load Current for Overload Relay #1

1. Press the LIST key to view the active full-load current setting

for overload relay #1. The setting should normally be the full

load current as shown on the motor nameplate (high speed

for two-speed machine). The range of possible settings and

the factory default value depend on the size displayed in F2

as follows:

Overload

Relay Size

Setting

Range

Step

Default

1A

0.3 - 1.5A

0.1A

0.3A

1B

1.2 - 6.0A

0.1A

1.2A

1C

4.8 - 24.0A

0.1A

4.8A

2A

10 - 36A

1A

10A

2B

10 - 45A

1A

10A

3

20 - 90A

1A

20A

4

40 - 135A

1A

40A

5

80 - 270A

1A

80A

6

160 - 540A

2A

160A

2. To change the setting, you must be in program mode.

3. Press the UP or DOWN key to scroll through the range of

settings until the selected setting appears.

4. Press the ENTER key to change the active setting to the

selected value. The display becomes blank while you hold

down the ENTER key, and the SAMMS-LV device stores the

new setting. (If you make an incorrect selection, repeat

steps 3 and 4).

5. To exit the program mode, press and hold the (F)unction key

for several seconds. The display will show “Prog.” Press the

UP or DOWN key to change to the display mode.

6. Press the (F)unction key to step through to another function.

F4A - 5A CT Primary Current Selection for Overload

Relay #1

SAMMS-LV is normally used with SAMMS sensors to provide

the current input signals to the device. Optionally, SAMMS-LV

may be used with conventional 5A secondary current trans-

formers.

1. Press the LIST key to view the sensor in use for overload

relay #1. If standard SAMMS sensors are used, the display

will read “OFF.” If 5A secondary CT’s are in use, the CT

primary current will be displayed.

2. To change the setting, you must be in program mode.

3. Press the UP or DOWN key to scroll through the range of

settings, until the selected setting appears on the display.

4. Press the ENTER key to change the active setting to the

selected setting. The display becomes blank while you hold

down the ENTER key and the SAMMS-LV device stores the

new setting.

5. To exit the program mode, press and hold the (F)unction key

for several seconds. The display will show “Prog.” Press the

UP or DOWN key to change to the display mode.

6. Press the (F)unction key to step through to another function.

F5 - Full-Load Current for Overload Relay #2

(SAMMS-LVX Only)

1. Press the LIST key to view the active full-load current setting

for overload relay #2. This setting should normally be the full

load current for the low speed shown on the motor name-

plate. The range of possible settings and the factory default

value depend on the size displayed in F3. The values are

similar to those found in the table in the procedure for F4. If

the control is not a two-speed control, OFF appears on the

display, and UP, DOWN and ENTER keys become disabled.

2. To change the setting, you must be in program mode.

3. Press the UP or DOWN key to scroll through the range of

settings until the selected setting appears.

4. Press the ENTER key to change the active setting to the

selected value. The display becomes blank while you hold

down the ENTER key, and the SAMMS-LVX device stores

the new setting. (If you make an incorrect selection, repeat

steps 3 and 4).

5. To exit the program mode, press and hold the (F)unction key

for several seconds. The display will show “Prog.” Press the

UP or DOWN key to change to the display mode.

6. Press the (F)unction key to step through to another function.

F5A - 5A CT Primary Current Selection for Overload

Relay #2 (SAMMS-LVX Only)

SAMMS-LV is normally used with SAMMS sensors to provide

the current input signals to the device. Optionally, SAMMS-LV

may be used with conventional 5A secondary current trans-

formers.

1. Press the LIST key to view the sensor in use for overload

relay #2. If standard SAMMS sensors are used, the display

will read “OFF.” If 5A secondary CT’s are in use, the CT

primary current will be displayed.

2. To change the setting, you must be in program mode.

3. Press the UP or DOWN key to scroll through the range of

settings, until the selected setting appears on the display.

4. Press the ENTER key to change the active setting to the

selected setting. The display becomes blank while you hold

down the ENTER key and the SAMMS-LVX device stores

the new setting.

5. To exit the program mode, press and hold the (F)unction key

for several seconds. The display will show “Prog.” Press the

UP or DOWN key to change to the display mode.