3 Operating the SAMMS-LV Device

To change the password:

1. Enter the password as described above.

2. With the password entered and the display showing “- - - -,”

press the UP or DOWN key to enter change mode. The

display reads “CHg.”

3. Press the ENTER key, and the display shows “HHH0,” the

prompt for entering the new password.

4. Enter the new password in the same way described above.

After entering all four digits of the new password, the display

will again display “HHH0.”

5. Enter the new password a second time. If it was entered

correctly the display reads “donE,” and pressing ENTER

gives access to the functions in program mode.

6. If the password was entered incorrectly, the display will read

“Err.” Press the ENTER key to return to program mode and

try again.

3.28.2 SAMMS-LV Functions

F0 - Ambient Temperature

1. Press the LIST key to view the ambient temperature se-

lected. The default value is 40° C and the range of possible

values is from 0° C to 70° C in increments of 5° C.

2. To change the setting, you must be in program mode.

3. Press the UP or DOWN key to scroll through the range of

settings, until the selected setting appears on the display.

4. Press the ENTER key to change the active setting to the

selected setting. The display becomes blank while you hold

down the ENTER key and the SAMMS-LV device stores the

new setting.

5. To exit the program mode, press and hold the (F)unction key

for several seconds. The display will show “Prog.” Press the

UP or DOWN key to change to the display mode.

F1 - Control Circuit Number and Incomplete Se-

quence Status

1. Press the LIST key to view the control circuit number

programmed at the factory. The circuit numbers range from

0 through 9999. (The UP, DOWN and ENTER keys become

disabled.)

2. For SAMMS-LVE, to change the settings, you must be in the

program mode. The available selections are program blocks

10-16 (refer to table 3.3). If you have loaded a custom circuit,

the designation for that circuit will be shown.

3. Press the UP or DOWN key to scroll through the range of

circuit numbers, until the desired circuit number appears on

the display.

4. Press the ENTER key to change the active setting to the

selected setting. The display becomes blank while you hold

down the ENTER key and the SAMMS-LV device stores the

new setting.

5. To exit the program mode, press and hold the (F)unction key

for several seconds. The display will show “Prog.” Press the

UP or DOWN key to change to the display mode.

6. Press the (F)unction key to step through to another function.

7. To enable or disable incomplete sequence, press the EN-

TER key for a period of one second or more. A “.” will be

displayed after the F1 on the HHC if incomplete sequence

is enabled. (The SAMMS-LV is shipped from the factory with

the incomplete sequence enabled.)

F2 - Size for Overload Relay #1

Overload relay #1 protects single-speed motors and two-

speed motors running on high speed. The possible values are

1A, 1B, 1C, 2A, 2B, 3, 4, 5, and 6. Use the following procedure

to display the size for overload relay #1.

1. Press the LIST key to view the size selected for overload

relay #1.

2. To change the setting, you must be in program mode.

3. Press the UP or DOWN key to scroll through the range of

settings, until the selected setting appears on the display.

4. Press the ENTER key to change the active setting to the

selected setting. The display becomes blank while you hold

down the ENTER key and the SAMMS-LV device stores the

new setting.

5. To exit the program mode, press and hold the (F)unction key

for several seconds. The display will show “Prog.” Press the

UP or DOWN key to change to the display mode.

F3 - Size for Overload Relay #2 (SAMMS-LVX Only)

Overload relay #2 protects two-speed motors running on low

speed. The possible values are 1A, 1B, 1C, 2A, 2B, 3, 4, 5, 6,

and OFF. OFF appears for single-speed motors. Use the

following procedure to display the size for overload relay #2.

1. Press the LIST key to view the size selected for overload

relay #2.

2. To change the setting, you must be in program mode.

3. Press the UP or DOWN key to scroll through the range of

settings, until the selected setting appears on the display.

4. Press the ENTER key to change the active setting to the

selected setting. The display becomes blank while you hold

down the ENTER key and the SAMMS-LV device stores the

new setting.

5. To exit the program mode, press and hold the (F)unction key

for several seconds. The display will show “Prog.” Press the

UP or DOWN key to change to the display mode.