Rs485 ports pinout, A.4 rs485 ports pinout – Schneider Electric Modbus Plus Network Bridge Multiplexer none User Manual
Page 98

Compatible Devices and Cables
88
88
31007492
A.4 RS485 Ports Pinout
This section covers the serial ports pinout for the following models:
Part Number
Mounting
Method
Operating
Power
(Nominal)
Modbus Plus
Network
Cable
Serial
Ports
Serial
Protocol
NW–BM85E485
Panel or Shelf
115/230 Vac or
24 Vdc
Single or Dual
RS485
Programmable,
User Defined
NW–BM85S485
Panel or Shelf
115/230 Vac or
24 Vdc
Single or Dual
RS485
Programmable,
User Defined
Figure 27 shows the pin configuration for the RS485 port connectors. If
you are fabricating cables for your application, the panel connector is a
DB9S.
The Modbus Plus inline connector (part number AS-MBKT-085) is an
acceptable substitute for an RS485 cable connector. Do not use a
Modbus Plus terminating connector (AS-MBKT-185) in this
application.
5 4 3 2 1
9 8 7 6
REAR PANEL
SERIAL PORT
CONNECTORS
Figure 27
Serial Ports Pinout – RS485
Pin
BM85 Direction
Purpose
1
––
Chassis ground
2
In/Out
Receive/Transmit A
3
In/Out
Receive/Transmit B
4 ... 9
––
not used