Modbus port indicator codes, 13 modbus port indicator codes – Schneider Electric Modbus Plus Network Bridge Multiplexer none User Manual
Page 64

Configuring the Modbus Models
31007492
54
3.13 Modbus Port Indicator Codes
If the BM85 detects a condition that prevents communication at its
Modbus Plus or Modbus ports, it shuts off all ports and displays an error
code pattern at its four Modbus port indicators.
Indicator layouts are shown in Figure 22.
The error pattern produces two 4-bit codes for two hexadecimal digits.
First, the indicators show a steady pattern for one second, indicating the
upper digit. Then they show a flashing pattern for one second with the
lower digit. The continuous and flashing patterns alternate repetitively.
Port 4 is the most significant bit in each code.
Indicators
Pattern
Hexadecimal Digit
4 – 3 – 2 – 1
Steady
Upper digit
4 – 3 – 2 – 1
Flashing
Lower digit
Hardware Error Codes: 11 ... 19 Hex
Code (Hexadecimal)
Meaning
11
PROM checksum error
12
RAM data test error
13
RAM address test error
14
Normal power down event
17
Bad or unexpected interrupt
18
EEPROM checksum error
19
Modbus port loopback error
Modbus Driver Error Codes: 24 ... 2E Hex
Code (Hexadecimal)
Meaning
24
Modbus transmit state error
25
Modbus receive state error
26
ASCII transmit communications state error
27
Transmit underflow error
28
RTU transmit communications state error
29
ASCII receive communications state error
2A
RTU receive communications state error
2B
Transmit communications state error
2C
Receive communications state error