beautypg.com

Replacing main power fuses, Replacing backplane fuses, Cleaning the enclosure window – SPX Cooling Technologies CS4000 User Manual

Page 95

background image

CS4000 Mini Controller with Ethernet

Page

8-2

T-38324-A

39-30-38324

Replacing Main Power Fuses

Main Power

F1 and F2

=

15A, 250V, SLO-BLO

Littelfuse 313015 or equivalent (part number 13-10-1015)

Refer to Figure 3-3 on page 3-4 to locate the main power fuses on the CS4000 Mini Controller bottom
panel.

Replacing Backplane Fuses

Backplane

F2 and F3

=

0.5A, 250V, subminiature PICO

Littelfuse 255.500 or equivalent (part number 13-10-4050)

NOTE: The backplane fuse, F2 (part number 13-10-4050), is not the

same as the main power fuse, F2 (part number 13-10-1015),
refer to
Replacing Main Power Fuses above. Make sure you
quote the correct part number when ordering replacements.

F4

5x20 mm, 1A, SLO BLO (SB) 250V

Littelfuse 239001 or equivalent (part number 13-10-61001)

Refer to Figure 3-8 on page 3-11 to locate the backplane fuses.

Cleaning the Enclosure Window

Use only water-based cleaners to clean the plastic window. Other solvents may damage the window.