beautypg.com

Slant/Fin Jaguar J-390 User Manual

Page 6

background image

Jaguar Model J-390

6

2. CONDENSATE REMOVAL SYSTEM

The Jaguar boilers is equipped with a built-in conden-
sation drain and trap. The trap must be filled with water.
DO NOT operate the boiler without filling the trap with
water to prevent flue gas discharge into space. Periodic
inspection should be made of this assembly for deterio-
ration of the tubing and to insure that the trap is not
plugged. If it is plugged or appears to have excessive
sediment in it, it should be removed from the drain
assembly, straightened out to clear the obstruction,
reformed, filled with water and reinstalled as before.
(See Figure 7).

Leave the top of the condensate drain tee open, to act
as a vacuum breaker. Do not allow any part of the
condensate removal system to be exposed to freezing
temperatures, or any other conditions that could cause
blockage.

If a neutralizing system is installed, the filter medium will
require periodic changing, to ensure it’s effectiveness.
Refer to the neutralizing unit’s manufacturers instruc-
tions, if available, or change the medium on an annual
basis.

3. PIPING INSPECTION

Look at all water piping. There should be no leaks or
signs of leaks at any pipe joints or around the boiler.

4. SYSTEM WATER PRESSURE INSPECTION

The boiler water pressure is indicated on the pressure
gage (See Figure 1 for location). The boiler water outlet
temperature is normally indicated on the temperature
display (See Figure 1 for location and Figure 9 for digits
illustration). For most installations, it should indicate

about 12 to 15 psi pressure when temperature is about
70 to 100F and from 15 psi to 25 psi when temperature
is up to 195˚F. FOR YOUR SYSTEM, there is one
correct pressure for each temperature. ASK YOUR
INSTALLER OR SERVICEPERSON TO EXPLAIN AND
SHOW YOU. Learn what normal pressure to look for. If
pressure increases from normal, the relief valve will
open to relieve the pressure. Call your service organiza-
tion if pressures are higher or lower than normal, and if
the relief valve spills water. Repair or adjustment is
needed.

5. UNUSUAL NOISE

Stand near the boiler and look and listen. As the burner
start and shut off, there should be no unusual noise.

6. BOILER ROOM AIR SUPPLY

Ample boiler room fresh air is required for combustion
(non-direct vent installation) and ventilation (direct-vent
installation).

Check air vents for continues positive supply of air as
required. Air needs are greatest in cold weather if boiler
installation is non-direct vent method. Air vents must be
open and free of obstruction.

Warning:

The flow of combustion and ventilating air to the

boiler should not be obstructed.

Warning:

If you find any problem during your inspection, call

for service immediately.

Figure 7. Condensate disposal system

NEUTRALIZING UNIT (IF REQUIRED)

CONDENSATE PUMP (IF REQUIRED)

DRAIN INSIDE BUILDING

PLASTIC TUBING

DRAIN VACUUM BREAKER, LEAVE OPEN