beautypg.com

Configuring the gateway – Schneider Electric Gateway LUFP7 User Manual

Page 61

background image

62

6. Configuring the Gateway

To check that these changes have been entered into the configuration, choose “Monitor” from the “Sub-
Network” menu again:

In point 6), you shall make sure that the total input and ouput sizes of the configured modules
are the same as the exchange sizes displayed in the “Sub-network Monitor.” In the current
example, “In Area 32 bytes” and “Out Area 36 bytes” imply that the modules combined under
SysCon must have a total of 16 IW and 18 OW.

4) Transferring this configuration to the gateway: Please see chapter 6.4 Transferring a Configuration to the

Gateway, page 47. Check that the configuration is valid (LED

s

G

ATEWAY

flashing green). However, the

gateway configuration is now different from the one taken into account by the Profibus-DP coupler with
respect to the gateway (difference in the total length of input data), the LED

q

F

IELDBUS

D

IAG

therefore

becomes flashing red at a frequency of 1 Hz, providing that the gateway is connected to the Profibus-DP
network and to its DPM1 master.

5) Saving this configuration to your PC’s hard disk.

6) Changing the number of data transmitted by the Profibus-DP coupler: Under SyCon, change the list of

modules configured for the gateway (see chapter 4.2.6 Editing and Configuring the Gateway, page 29). Since
we have added 4 bytes after the output data in the gateway memory, the coupler should be configured to
issue an additional 4-byte output data block for the gateway.