Figure 22

Controller Check (for all EZ-5 units and for EZ-3 units built after Jan. 15, 2001)

C98

EZ STEAMER LOGIC CHART

Step

Door Switch (SW2) #8

Float Switch (SW1) #7-#9

Contactor Heaters (Load 2) #5

Notes

1

Door Open

No Pressure, Up Position

Switch Closed

Heaters Off

2

Door Open to Close

No Pressure, Up Position

Switch Closed

Heaters On for 60 Seconds, then

Step 3 or 4

Even if float switch
opens with pressure.

3

Door Closed

No Pressure, Up Position

Switch Closed

Heaters On

4

Door Closed

Pressurized, Down Position

Switch Open

Heaters Off

5

Normal Cycle Operation

Door Closed

When Pressure Drops, Goes

to Up Position, Switch Closes

Heaters On for 10 Seconds, then

Step 3 or 4

Even if float switch
opens with pressure.

1. Disconnect power at circuit breaker.

2. Remove control panel, but leave plugged in.

3. Disconnect wire C98 from controller.

4. Reconnect power.

5. Use a spacer to hold door switch in closed position. Contactor should actuate and then deactuate

in less than 60 seconds.

6. If contactor fails to actuate (or actuates but fails to deactuate), replace controller.

7. With spacer still in place and door open, momentarily reconnect wire C98 and then disconnect.

8. Controller should actuate, then deactuate 10 seconds after C98 is disconnected.

9. If contactor fails to actuate (or actuates but fails to deactuate), replace controller.