beautypg.com

SUPER MICRO Computer AS1020S-8 User Manual

Page 19

background image

Chapter 2: Server Installation

2-3

Rack Mounting Considerations

Ambient Operating Temperature

If installed in a closed or multi-unit rack assembly, the ambient operating tem-

perature of the rack environment may be greater than the ambient temperature

of the room. Therefore, consideration should be given to installing the equip-

ment in an environment compatible with the manufacturer’s maximum rated

ambient temperature (Tmra).

Reduced Airfl ow

Equipment should be mounted into a rack so that the amount of airfl ow required

for safe operation is not compromised.

Mechanical Loading

Equipment should be mounted into a rack so that a hazardous condition does

not arise due to uneven mechanical loading.

Circuit Overloading

Consideration should be given to the connection of the equipment to the power

supply circuitry and the effect that any possible overloading of circuits might

have on overcurrent protection and power supply wiring. Appropriate consid-

eration of equipment nameplate ratings should be used when addressing this

concern.

Reliable Ground

A reliable ground must be maintained at all times. To ensure this, the rack itself

should be grounded. Particular attention should be given to power supply con-

nections other than the direct connections to the branch circuit (i.e. the use of

power strips, etc.).