locatInG the BoIler

approVals

Model and ratInG

facts to consIder aBout the locatIon

Carefully choose a location for the boiler. The placement is a very

important consideration for the safety of the occupants in the building

and for the most economical use of the appliance.

Whether replacing an old boiler or putting the boiler in a new location,

the following critical points must be observed. The boiler must be

located:

1. On a level surface. Shim the channel type skid base as

necessary if levelling is required.

2. Near a floor drain. The boiler should be located in an area

where leakage of the tank or connections will not result in

damage to the area adjacent to the boiler or to lower floors of

the structure.

3. The discharge opening of the temperature and pressure relief

valve should always be piped to an open drain.

4. Close to the point of major hot water usage and the power supply.

Hot water piping and branch circuit wiring should be as short as possible.

Insulate hot and cold water piping where heat loss and condensation

may be a problem.

Boiler construction permits installation, maintenance, and service

work to be performed through panels located in multiple sides of the

boiler.

Suggested clearances from adjacent surfaces are 12 inches on top,

30 inches in front for access to the unit.

The boiler may be installed in a confined space if adequate ventilation

is provided.

The temperature of the space in which the boiler is installed must not

go below 32°F or above 122°F.