11
▓
▓
▓
▓
SMASK
Description
This command enables you to read system status showing by a hexadecimal number that
represents the 8 bits corresponding binary numbers.
bit
Corresponding to:
Description
0
Power 1
If there is a power fail occurring on Power 1, bit 0 will be
set as 1.
1
Power 2
If there is a power fail occurring on Power 2, bit 1 will be
set as 1.
2
Master Ring Switch
If his Switch is the master Ring Switch (the Master LED
indicator will be “on”) bit 2 will be set as 1.
3
Relay output status
If the relay output is activated, bit 3 will be set as 1.
Example
Power2 fail occurring, and the Switch is the Master of the topology.
▓
▓
▓
▓
HMIVALUE [value1] [value2]
Description
This command enables you to configure the Switch operation modes.
Parameters
Parameter Description
Value 1
bit0 : set 1 to enable ring pair 1.
bit1 : set 1 to enable ring pair 2.
bit2 : set 1 to enable STP Protocol. otherwise is Cyber-Ring Protocol
bit3 : set 1 to force Switch as the Master of topology.
Value 2
Reserved.