Manitowoc Ice Chiplet QC0700 User Manual
Page 25
Section 2
Installation Instructions
Part Number 000002688
2-15
C. SUCTION LINE OIL TRAPS
0 to 20 feet (0 to 6.1 m) Rise: The ice machine head
section has one oil trap built in which allows for a
maximum condenser rise of 20 feet (6.1 m) without
additional traps in the suction line.
21 to 35 feet (6.4 to 10.7 m) Rise: The suction line
requires an additional Oil Trap (“S” type) to be installed.
Install the trap as close as possible to midpoint between
the ice machine head section and remote condensing
unit. S-Trap Kits are available from Manitowoc (refer to
chart).
Manitowoc S-Trap Kit
Service Loop
A service loop in the line set permits easy access to the
ice machine for cleaning and service.
•
The supplied service loop is an installation
requirement.
•
A service loop is not considered an oil trap.
•
The service loop is not included when calculating
length, rise or drop of the tubing run.
•
Do not use hard rigid copper for the service loop.
Step 3 Lengthening or Reducing Line Set Lengths
When the line set required shortening or lengthening, do
so before connecting the line set to the ice machine
head section or the remote condensing unit.
Continued on Next Page...
! Caution
Do not form unwanted traps in refrigeration lines.
Never coil excess refrigeration tubing.
Model
S-Trap Kit
Number
Tubing Size
QF2300
K00166
3/4 inch
(19.1 mm)
21’ OR MORE
RISE
ADDITIONAL
TRAP KIT
REQUIRED
SV1751
SV1760
! Caution
If a line set has a rise followed by a drop, another rise
cannot be made. Likewise, if a line set has a drop
followed by a rise, another drop cannot be made.
! Caution
Do not form unwanted traps in refrigeration lines.
Never coil excess refrigeration tubing.