beautypg.com

Appendices, 1 technical specifications – MGE UPS Systems 5000 RT User Manual

Page 35

background image

34008030EN/AA

- Page 35

8. Appendices

8.1 Technical specifications

(1) If the output voltage is 200V - 250V, the output power is 4500VA / 4000W.
(2) With one EXB module or more, the standard output power is 5000VA / 4000W.
(3) Values for 70% / 100% of UPS output.
(4) Programmable: 200V / 208V / 220V / 230V / 240V / 250V using the UPS Config software.
(5) Frequency-converter mode is programmable using the UPS Config software.

Pulsar MX 4000

Pulsar MX 5000

Pulsar MX EXB

Output power

4000 VA /

3600 W

5000 VA

(1)

/

4500 W

(2)

Electrical supply network

Rated input voltage

Input voltage range

Frequency

Power factor

Leakage current

Single phase 230 V

120 / 156 V to 280 V

(3)

50/60 Hz (autoselection)

> 0.99

7 mA max.

Load output

Voltage

Frequency

Harmonic distortion

Overload capacity

Single phase 230 V ±3%

(4)

50/60 Hz ±0,5%

(5)

< 3%

105% continuous, 110% 2min,

125% 1min, > 150% 0.5s

Battery

15 x 12V - 5 Ah,

sealed lead acid,

maintenance free

15 x 12V - 5 Ah,

sealed lead acid,

maintenance free

Two 15 x 12 V - 5 Ah

strings, sealed lead acid,

maintenance free

Environment

Operating temperature range

Relative humidity

Storage temperature range

Altitude

Noise level

0°C to 40°C

20% to 90% (non-condensing)

-25°C to 40°C

0 to 1000 m without derating

< 45 dBA

This manual is related to the following products: