2. Installation

2.6 Required protective devices and cable cross-sections

Recommended upstream protection

Recommended downstream protection

Required cable cross-sections

Terminal-block cable capacity: 6 mm

2

, solid or stranded wire (maximum 8 mm

2

or AWG 8).

Capacity for earthing conductor: 6 mm

2

, solid or stranded wire (maximum 8 mm

2

or AWG 8).

UPS power rating

Upstream circuit breaker

The indicated protection ensures
discrimination for each output circuit
downstream of the UPS.
If these recommendations are not followed,

protection discrimination is not achieved and
may result in a potential power interruption to
the connected devices.

4000 RT

D curve - 32A

5000 RT

D curve - 32A

UPS power rating

Downstream circuit breaker

The indicated protection ensures
discrimination for each output circuit
downstream of the UPS.
If these recommendations are not followed,

protection discrimination is not achieved and
may result in a potential power interruption to
the connected devices.

4000 RT

Z curve - 10A

C curve - 4A

5000 RT

Z curve - 10A

C curve - 6A

G N L

N

L

2 poles circuit breaker

To UPS Normal AC source