4. Access to measurements and personalisation data

4.4 UPS set-up

Local settings

Output settings

ON/OFF settings

Function

Factory setting

Options

Language

English

French, German, Italian, Portuguese, Spanish

Date / Time Format

International
(DD-MM-YYYY/HH :MM)

US (MM-DD-YYYY/HH:MM AM/PM)

Date / Time Change

GMT + 1
(Continental Europe)

MM-DD-YYYY/HH :MM adjustable

Audible Alarm

Yes

No

Function

Factory setting

Options

Comments

Output Voltage

230 V

200 V / 208 V / 220 V /
240 V / 250 V

Freq Converter

Disable

Enable

Output Frequency

50 Hz

60 Hz

User selectable under frequency-
converter mode

Eco Mode

DisablE

Enable

See glossary

Slew Rate

1 Hz / sec.

0.5 Hz / sec.

Bypass Transfer
If bypass Ac nok?

Yes

No

Transfer to bypass if Normal AC
source is out of tolerance

Interrupt Time

10 ms

20 ms, ...... , 200 ms

Break time calibration during load
transfer on Normal AC source out of
tolerance

Overload Prealarm

105 %

40 %, 50 %, 70 %

Alarm if threshold is overrun

Redundancy Mode

No

Yes

On parallel sequence : Alarm if
redundancy loss

Function

Factory setting

Options

Comments

Cold Start

Disable

Enable

Start on battery

Forced Reboot

Enable

Disable

Enables automatic restart of the
system even if Normal AC source is
restored before the end of the
shutdown sequence

Auto Restart

Enable

Disable

UPS restarts automatically when
Normal AC source is restored

Energy Saving

Disable

Enable

Automatic shutdown on battery if
output load level < 10 %

Sleep Mode

Enable

Disable

Remote Command

Enable

Disable

Enables consideration of shutdown
or restart orders from software to be
authorised