Access to measurements and personalisation data, 4 ups set-up – MGE UPS Systems 5000 RT User Manual
Page 26
34008030EN/AA
- Page 26
4. Access to measurements and personalisation data
4.4 UPS set-up
Local settings
Output settings
ON/OFF settings
Function
Factory setting
Options
Language
English
French, German, Italian, Portuguese, Spanish
Date / Time Format
International
(DD-MM-YYYY/HH :MM)
US (MM-DD-YYYY/HH:MM AM/PM)
Date / Time Change
GMT + 1
(Continental Europe)
MM-DD-YYYY/HH :MM adjustable
Audible Alarm
Yes
No
Function
Factory setting
Options
Comments
Output Voltage
230 V
200 V / 208 V / 220 V /
240 V / 250 V
Freq Converter
Disable
Enable
Output Frequency
50 Hz
60 Hz
User selectable under frequency-
converter mode
Eco Mode
DisablE
Enable
See glossary
Slew Rate
1 Hz / sec.
0.5 Hz / sec.
Bypass Transfer
If bypass Ac nok?
Yes
No
Transfer to bypass if Normal AC
source is out of tolerance
Interrupt Time
10 ms
20 ms, ...... , 200 ms
Break time calibration during load
transfer on Normal AC source out of
tolerance
Overload Prealarm
105 %
40 %, 50 %, 70 %
Alarm if threshold is overrun
Redundancy Mode
No
Yes
On parallel sequence : Alarm if
redundancy loss
Function
Factory setting
Options
Comments
Cold Start
Disable
Enable
Start on battery
Forced Reboot
Enable
Disable
Enables automatic restart of the
system even if Normal AC source is
restored before the end of the
shutdown sequence
Auto Restart
Enable
Disable
UPS restarts automatically when
Normal AC source is restored
Energy Saving
Disable
Enable
Automatic shutdown on battery if
output load level < 10 %
Sleep Mode
Enable
Disable
Remote Command
Enable
Disable
Enables consideration of shutdown
or restart orders from software to be
authorised