beautypg.com

Troubleshooting – MGE UPS Systems 5000 RT User Manual

Page 28

background image

34008030EN/AA

- Page 28

5. Troubleshooting

5.1 Troubleshooting LEDS (21) and (22)

5.2 Troubleshooting not requiring MGE UPS SYSTEMS after-sales support

If

LED

(21) is ON:

the equipments are protected by the UPS
but the operation is downgraded.

If

LED

(22) is ON:

the equipments are no longer protected
by the UPS.

Press the escape button (24) to stop the
audible alarm.

Note :
In case of

"

MULTIPLE FAULT

"

, press the

"

Enter

"

button (27) and the scroll button (25)

to get access to further details.
In case of

"

LCM WARNING

"

, refer to LCM

section (see section 6).

Press the

"

Enter

"

button (27) to display the details below :

Displayed details

Signification

Correction

NO BATTERY

The battery is incorrectly connected

Check battery connections

I/O BAD CONNECTION

AC source is not connected to the correct
terminals

Check AC wiring

NO POWER MODULE

The power sub-module is not inserted

Check power sub-module connections (see
section 7.1)

NO BATTERY MODULE

The battery sub-module is incorrectly
connected

Check battery connections (see section 7.2)

INV THERM OVERLOAD

The UPS shuts down automatically because
of a major overload.

Check the power drawn by the connected
devices and disconnect any non-priority
devices.

INVERT LIMITATION

Short circuit conditions on output devices

Check the installation at the UPS output
(wiring, fault equipment)

21

20

22

ESC

25

LOAD PROTECTED

x.xkVA / xxx% LOADED

ENVIRONMENT FAULT

SINGLE UPS

27

24

ESC

LOAD PROTECTED

x.xkVA / xxx% LOADED

x x x x x x x x FAULT

SINGLE UPS

This manual is related to the following products: