Melsec-a – MITSUBISHI ELECTRIC AJ65SBT-64AD User Manual
Page 67
Appendix - 2
MELSEC-A
APPENDIX
(2) Precautions for replacing the conventional product (AJ65BT-64AD)
with the AJ65SBT-64AD
In the existing system using the conventional product (AJ65BT-64AD), the
following instructions must be noted when changing the AJ65BT-64AD for the
AJ65SBT-64AD.
(a) Since the AJ65SBT-64AD occupies one station (the AJ65BT-64AD occupies
two stations), the station information setting in the network parameters must
be changed.
(b) As the remote I/O signals and remote register settings are different between
the two models, the program of the conventional model cannot be utilized.
(c) Because of the differences in shape and layout between the terminal blocks,
you cannot use the terminal block of the conventional module as it is.
(d) The offset/gain setting method differs. For details, refer to Section 4.4.
(e) The ways to set the station number and transmission speed setting switches
are different. For details, refer to Section 4.3.