6 TROUBLESHOOTING

6.4 Troubleshooting for the Case where the "ERR." LED of the Master Station Flickers

The "ERR"LED on the
master station is flashing

Do the parameter

setting and the installed system

configuration match

properly?

Are the master

station link special registers

SW0080 to SW0083 (other station

date link status)

turned on?

Are the master

station link special registers

SW0098 to SW009B (station

number overlap status)

turned on?

Check the module for which
SW0098 to SW009B are on

Are the

station number setting

switches set

properly?

Set the station number setting
swiches properly

Revise the parameter settings
or installed system configuration

Master station malfunction

Check the module for which
SW0080 to SW0083 are on

Is the power on?

Turn on the power

Corresponding module
malfunction

Turn on the power again

Is the "POWER" LED lit?

Is the supplied

power within the specified

range

Set the supplied voltage to
within the specified range

Corresponding module
malfunction

1

2

3

Check on master station side

Check on slave station side

N

N

N

N

Y

Y

Y

N

N

Y

Y

Y

Y

N