beautypg.com

Melsec-a – MITSUBISHI ELECTRIC AJ65SBT-64AD User Manual

Page 29

background image

3 - 14

MELSEC-A

3 SPECIFICATION

3.6.2 A/D conversion enable/prohibit specification (Address RWwm)

(1) Set whether A/D conversion is enabled or disabled per channel.

(2) By setting the unused channels to conversion prohibit, the sampling cycle can be

shortened.

Example) The sampling cycle when only channels 1 and 3 are set to A/D

conversion enabled:

2 (Number of channels enabled) × 1ms (Conversion speed at one channel) = 2ms

(3) Operation is performed according to the setting made for the leading edges of

initial data setting request flag (RY(n+1)9).

(4) The default setting is A/D conversion disable for all channels.

b15

b14

b13

b12

b11

b10

b9

b8

b7

b6

b5

b4

b3

b2

b1

CH.2 CH.1

b0

Ignored

CH.3

CH.4

1: Enable A/D conversion
0: Prohibit A/D conversion