3 - 13

MELSEC-A

3 SPECIFICATION

3.6 Remote Register

The AJ65SBT-64AD has a remote resister for data communication with the master

module. The remote register allocation and data structures are described.

3.6.1 Remote register allocation

The remote register allocation is shown in Table 3.6.

Table 3.6 Remote register allocation

Communication direction

Address

Description

Default value

Reference section

RWwm

A/D conversion enable/prohibit specification

0

Section 3.6.2

RWwm+1

Input range setting

0

Section 3.6.3

RWwm+2

Moving average processing count setting

0

Section 3.6.4

Master

Remote

RWwm+3

Reserved

0

——

RWrn

CH.1 digital output value

0

RWrn+1

CH.2 digital output value

0

RWrn+2

CH.3 digital output value

0

Remote

Master

RWrn+3

CH.4 digital output value

0

Section 3.6.5

m, n: Address allocated to the master module by the station number setting.

POINT

Do not read or write data from or to the reserved area of the remote register. If data

is read or written, we cannot guarantee the functions of the AJ65SBT-64AD.