2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

3-4

MITSUBISHI ELECTRIC 2033C SERIES UPS

NOTES:

1. Confirm that all UPS internal contactors (breakers) "CB1", "CB2", and

"CB3" are open before energizing UPS.

2. UPS power terminals are supplied with stud type fittings. It is

recommended that compression lugs be used to fasten all input/output
power cables. Refer to Table 3.5 for recommended compression lugs and
appropriate crimping tool

Table 3.4 Recommended Cable Size and Torque Requirements

UPS

Input Side * 1

Output Side * 1

Capacity (kVA)

Cable *

2

Size

Torque

(in. lbs)

Cable *

2

Size

Torque

(in. lbs)

7.5kVA (208V)

8 AWG or larger

180 in. lbs

8 AWG or larger

180 in. lbs

10kVA (208V)

8 AWG or larger

180 in. lbs

8 AWG or larger

180 in. lbs

15kVA (208V)

8 AWG or larger

180 in. lbs

8 AWG or larger

180 in. lbs

20kVA (208V)

6 AWG or larger

180 in. lbs

6 AWG or larger

180 in. lbs

30kVA (208V)

2 AWG or larger

180 in. lbs

2 AWG or larger

180 in. lbs

40kVA (208V)

2/0 AWG or larger

180 in. lbs

2/0 AWG or larger 180 in. lbs

50kVA (208V)

2/0 AWG or larger

180 in. lbs

2/0 AWG or larger 180 in. lbs

*1 - Voltage drop across power cables not to exceed 3% of nominal source voltage.

*2 - Allowable ampere ratings based on 90゚C insulation at an ambient temperature of 30゚C.

No more than 3 conductors in a raceway without de-rating. Copper conductors assumed.

TABLE 3.5 Crimp Type Compression Lug

WIRE

SIZE

WIRE

STRAND

RECOMMENDATION

CRIMP TOOL REQUIRED

BURNDY TYPE Y35 OR Y46

(CODE)

CLASS

VENDOR

CAT. NO.

COLOR KEY

DIE INDEX

8 B

BURNDY

YA8C-L2

RED

49

6

B

BURNDY

YA6C-L3

BLUE

7 / 374

4

B

BURNDY

YA4C-L3

GRAY

8 / 346

2 B

BURNDY

YA2C-L

BROWN

10

2/0 B

BURNDY

YA26-L3

BLACK

13

NOTE: When using crimp type lugs, the lugs should be crimped to the

specifications given in the manufacturer's instructions for both crimp tool
and lug
.