2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-4
MITSUBISHI ELECTRIC 2033C SERIES UPS
NOTES:
1. Confirm that all UPS internal contactors (breakers) "CB1", "CB2", and
"CB3" are open before energizing UPS.
2. UPS power terminals are supplied with stud type fittings. It is
recommended that compression lugs be used to fasten all input/output
power cables. Refer to Table 3.5 for recommended compression lugs and
appropriate crimping tool
Table 3.4 Recommended Cable Size and Torque Requirements
UPS
Input Side * 1
Output Side * 1
Capacity (kVA)
Cable *
2
Size
Torque
(in. lbs)
Cable *
2
Size
Torque
(in. lbs)
7.5kVA (208V)
8 AWG or larger
180 in. lbs
8 AWG or larger
180 in. lbs
10kVA (208V)
8 AWG or larger
180 in. lbs
8 AWG or larger
180 in. lbs
15kVA (208V)
8 AWG or larger
180 in. lbs
8 AWG or larger
180 in. lbs
20kVA (208V)
6 AWG or larger
180 in. lbs
6 AWG or larger
180 in. lbs
30kVA (208V)
2 AWG or larger
180 in. lbs
2 AWG or larger
180 in. lbs
40kVA (208V)
2/0 AWG or larger
180 in. lbs
2/0 AWG or larger 180 in. lbs
50kVA (208V)
2/0 AWG or larger
180 in. lbs
2/0 AWG or larger 180 in. lbs
*1 - Voltage drop across power cables not to exceed 3% of nominal source voltage.
*2 - Allowable ampere ratings based on 90゚C insulation at an ambient temperature of 30゚C.
No more than 3 conductors in a raceway without de-rating. Copper conductors assumed.
TABLE 3.5 Crimp Type Compression Lug
WIRE
SIZE
WIRE
STRAND
RECOMMENDATION
CRIMP TOOL REQUIRED
BURNDY TYPE Y35 OR Y46
(CODE)
CLASS
VENDOR
CAT. NO.
COLOR KEY
DIE INDEX
8 B
BURNDY
YA8C-L2
RED
49
6
B
BURNDY
YA6C-L3
BLUE
7 / 374
4
B
BURNDY
YA4C-L3
GRAY
8 / 346
2 B
BURNDY
YA2C-L
BROWN
10
2/0 B
BURNDY
YA26-L3
BLACK
13
NOTE: When using crimp type lugs, the lugs should be crimped to the
specifications given in the manufacturer's instructions for both crimp tool
and lug.