MITSUBISHI ELECTRIC 2033C SERIES UPS

MITSUBISHI
ELECTRIC

2033C SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

2-7

B) Input Contacts (for remote access of UPS)

External contacts are provided by the user of the UPS system. The terminal voltage at the

UPS is 24Vdc. External dry contacts are to be provided accordingly.

NOTE: Do not apply voltages to remote access input terminals. Damage to UPS may result.

Refer to Figure 2.8 for a typical wiring configuration. Although this figure shows the

emergency stop configuration, the same wiring arrangement is used for battery

temperature high. See below for terminal connection details.

FIGURE 2.8 Remote "Stop" Contact Connections

Details of input contacts for remote access :

Terminals 1 to 2

“Emergency Stop” contact input

Used to perform a remote UPS emergency power off (EPO).

The load will be dropped.

Terminals 3 to 4

“Battery Temp. High” contact input

Input fed by a thermocouple that monitors battery temperature. The converter

float voltage level is reduced for battery over-temperature conditions. The

external thermocouple will be user supplied

NOTE : In all cases, a switch having a protective cover is recommended in order to reduce

possibility of accidental operation.

User supplied

Relay Coil current : 8.3mA

Use Momentary Switches

UPS Cabinet

External to UPS
Cabinet

Relay

Coil

24 VDC

Emergency

Stop

2