WARNING:

PERFORM THE WIRING INSTALLATION WITH THE POWER SOURCE OFF.

NEVER ROUTE THE SHD30 MODELS OVERSPEED OUTPUT LEADS WITH PRIMARY IGNITION WIRING.

44

50

44

45

45

46

46

47

47

48

48

49

49

50

LCDT
Terminal Block

SHD30

CD Ignition
90-350VDC

+

IGN

C

NC

+

N.O.

1

2

3

4

1

2

3

4

5

6 7

TB1

TB2

TB2

1 NO
2 C
3 NC
4 +Overspeed SCR
5 –Overspeed SCR
6

Reset Hourmeter

7

TB1

1 MPU +
2 MPU –
3 NEG 90-300vdc
4 POS 90-300vdc

5-120Vrms

46

Back of MARK

IV

CD Ignition
90-350VDC

+

IGN

C

NC

+

NO

1

2 3

4

1

2 3

4

5

6 7

TB1

TB2

TB2

1 NO
2 C
3 NC
4 +Overspeed SCR
5 –Overspeed SCR
6

Reset Hourmeter

7

TB1

1 MPU +
2 MPU –
3 NEG 90-300vdc
4 POS 90-300vdc

5-120Vrms

46

45

47

48

49

LCDT
Terminal Block

50

RESET

CD Ignition
90-350VDC

+

IGN

C

NC

+

NO

1

2

3

4

1

2

3

4

5

6 7

TB1

TB2

TB2

1 NO
2 C
3 NC
4 +Overspeed SCR
5 –Overspeed SCR
6

Reset Hourmeter

7

TB1

1 MPU +
2 MPU –
3 NEG 90-300vdc
4 POS 90-300vdc

5-120Vrms

OVERSPEED OUTPUT WIRING

continued

Figure 8:

SHD30 models Normally Closed Relay output to LCDT-NC

Figure 7:

SHD30 models Normally Open SCR output to MARK IV

Figure 9:

SHD30 models Normally Open S.C.R. output to LCDT-NO

SHD30 models to be installed in accordance with NEC code for
Cl. I, Div. 2 Grps. C & D hazardous locations.

SHD30 to be installed in
accordance with NEC code
for Cl. I, Div. 2 Grps. C & D
hazardous locations.

SHD30 models to be installed in accordance with NEC code for
Cl. I, Div. 2 Grps. C & D hazardous locations.

1

G

2

3

1

G

2

3

SW

ALT 2

ALT 1

GRD

Pressure

Overspeed

Level

1

2

3

1

2

3

4

5

6

65-02-0155

Adapter

Package

Emergency
Stop Switch

Frame Ground

307PHCD
TATTLETALE

®

Connect to
Good Engine
Ground

CD Ignition
90-350 VDC

+

SWICHGAGE

®

1

G

2

3

SHD30

+

C

NC

+

NO

1

2

3

4

1

2

3

4

5

6 7

TB1

TB2

TB2

1 NO
2 C
3 NC
4 +Overspeed SCR
5 –Overspeed SCR
6

Reset Hourmeter

7

TB1

1 MPU +
2 MPU –
3 NEG 90-300vdc
4 POS 90-300vdc

5-120Vrms

1

G

2

3

1

G

2

3

1

G

2

3

SW

ALT 2

ALT 1

GRD

Pressure

Overspeed

Level

1

2

3

1

2

3

4

5

6

65-02-0127

Adapter

Package

Emergency
Stop Switch

Frame Ground

307PHCD
TATTLETALE

®

Connect to
Good Engine
Ground

CD Ignition
90-350 VDC

+

SWICHGAGE

®

SHD30

+

C

NC

+

NO

1

2

3

4

1

2

3

4

5

6 7

TB1

TB2

TB2

1 NO
2 C
3 NC
4 +Overspeed SCR
5 –Overspeed SCR
6

Reset Hourmeter

7

TB1

1 MPU +
2 MPU –
3 NEG 90-300vdc
4 POS 90-300vdc

5-120Vrms

Figure 10:

SHD30 models with Normally Open S.C.R. output typical

wiring for negative ground ignition systems.

Figure 11:

SHD30 models with Normally Open S.C.R. output typical

wiring for positive ground ignition systems.

Shown below is the SHD30 models with SCR output connected to TAT-
TLETALE

®

magnetic switches and SWICHGAGE

®

instruments using an

adapter package. Figure 10 shows a typical wiring for negative ground
ignition. Figure 11 shows a typical wiring for positive ground ignition.

TYPICAL WIRING FOR CONTROL PANEL

SHD30 models to be installed in accordance with NEC code
for Class I, Div. 2 Grps. C & D hazardous locations.

SHD30 models to be installed in accordance with NEC code
for Class I, Div. 2 Grps. C & D hazardous locations.

WARNING: Overspeed relay contact for use with Frank W.
Murphy Mfr. non-incendive or intrinsically safe products only.