beautypg.com

GSW JWF307 User Manual

Page 9

background image

– 9 –

Burning Equipment (NFPA 31)” (as applicable), local

codes and the manufacturer’s instructions. The burner

should be installed only by a qualified Oil-Burner Technician.

Oil Supply Connections

All aspects of oil tank location and installation, tank size, oil

piping supply and burners, including any fittings, valves, fil-

ters or any fuel handling components must comply with:

• “Installation Code for Oil Burning Equipment

(CAN/CSA-B139)”, (Canada).

• “Standard for the Installation of Oil-Burning

Equipment. (NFPA 31)”, (USA).

• Local codes and regulations.

• Information provided with burner and fuel pump.

Install the oil supply tank with fill and vent lines of adequate

capacity as shown in Figure 4. When an appliance using a

float valve between the supply tank and the burner is con-

nected to a supply tank over 9 Canadian gallons capacity, a

valve operated by a fusible link, shall be installed in the fuel

line adjacent to, and upstream from, the float valve. If any

part of fuel oil tank is above level of burner, an anti-siphon

device must be used to prevent flow of oil in case of oil line

break. Support the oil lines as required by applicable codes.

Make tank connections with swing joints or copper tubing to

prevent breaking in case the tank settles. Make the swing

joints so they will tighten as tank settles. Non-hardening pipe

joint compounds should be used on all threads. Do not use
Teflon® tape as an oil pipe sealant. It can cause valves to

fail creating hazards. Do not use compression fittings.

Underground pipe must be run in a casing to prevent oil

leaking into ground or under floor. Check local codes for

more information.

Water Supply Connections

Pipes and fittings should be installed in as shown in the

installation drawing (Figures 7 & 8). Install a shut-off valve in

the cold water supply line in close proximity to the cold inlet

of the water heater. This valve is for use only when servic-

ing the heater and must be kept open during the heater’s

operation. The water connection fittings (nipples) may con-

tain a non-metallic lining to minimize corrosion and some

models include non-metallic heat traps. These appear like

pink or blue coloured plugs in the fitting. Do not attempt to

pry these plugs loose or damage them. DO NOT APPLY

HEAT DIRECTLY TO THE WATER HEATER NIPPLES. If

copper piping is used, solder a piece of tubing to a threaded

adaptor before screwing the adaptor to the nipples. Use only

solder approved for use with potable water systems. Use a

good grade of pipe joint compound, certified for use with

potable water, on the threaded fittings. Be sure all fittings are

drawn up tight.

NOTE: Rear and Combination flue heaters are equipped

with a combination cold water inlet/drain valve.

Temperature and Pressure (T&P) Relief Valve

To reduce the risk of excessive pressures and temperatures

in this water heater, install temperature and pressure pro-

tective equipment as required by local codes. It should be no

less than a combination Temperature and Pressure (T&P)

Relief Valve certified by a nationally recognized testing lab-

oratory that maintains periodic inspection of production of

listed equipment or materials, as meeting the requirements

of the latest edition of ANSI Z21.22: Requirements for

Relief Valves and Automatic Gas Shut-off Devices for

Hot Water Supply Systems. This valve must be marked

with a maximum set pressure not to exceed the marked

MAXIMUM working pressure of the water heater (150 psi

(1034 kPa). The function of the temperature and pressure

relief valve is to discharge water in quantities, should cir-

cumstances demand. To prevent property damage, bodily

injury or hazard to life the relief valve must be allowed to dis-

charge water in the event of excessive temperature or pres-

sure developing in the water heater. If the discharge tube is

not directed to a drain as shown in Figures 7 & 8 or by other

suitable means, the resulting water flow may cause sub-

stantial property damage. Install the T&P valve into the

opening provided and marked for this purpose in the water

heater, and orient it or provide tubing so that any discharge

from the cannot contact any live electrical part. Do not con-

nect discharge directly to a drain.

the discharge line:

must not be smaller than the outlet pipe size of the

relief valve,

• opening must not be threaded, blocked, plugged,

capped, reduced in size or restricted in any manner

under any circumstances,

must be made of material capable of withstanding

100°C (212°F) without distortion,

must be installed so as to allow complete drainage of

both the temperature and pressure relief valve and dis-

charge line,

must terminate near a floor drain or other suitable loca-

tion not subject to blocking or freezing, and

must exit only within 150mm (6 in.) above, or at any dis-

tance below the structural floor.

NOTE: Rear and Combination flue units must be fitted with

a T&P Relief Valve WATTS type 40XL-5 or equivalent.

Failure to install and maintain a new, properly listed

temperature and pressure relief valve will release the

manufacturer from any claims which may result from

excessive temperature or water pressure.

Closed Water Systems

During the heating cycle of the water heater the water

expands creating a pressure build-up in the water system.

The water supply meter may contain a check valve or back

flow preventer. This will create a closed water system. A

Temperature and Pressure (T&P) Relief Valve (150 psi

(1034 kPa) maximum pressure setting, must be installed in

the system (see “Temperature and Pressure (T&P) Relief

Valve” section). To prevent the T&P valve from discharging

hot water, the loss of energy and reduce the possible build-

This manual is related to the following products: