beautypg.com

GSW JWF307 User Manual

Page 7

background image

– 7 –

appliances in the enclosure, freely communicating with inte-

rior areas that have in turn adequate infiltration from the out-

side. It shall also have a combustion air supply opening so

that the total air received through the opening will be at least

as much as would be admitted by openings having a total
free area of 4.5 cm

2

/kWh (1 in

2

/5000 Btu/h) of the total input

rating of all oil-fired appliances in the enclosure.

Indoor Combustion & Ventilation Air

(Confined space)

A heater installed in a confined space and that obtains all of

its air for combustion and ventilation from within the condi-

tioned space of the building shall be provided with two per-

manent openings, one near the top of the enclosure and

another near the bottom. Each opening shall have a free
area of not less than 19.5 cm

2

/kWh (1 in

2

/1000 Btu/h) of the

total input rating of all appliances in the enclosure, freely

communicating with interior areas that have in turn adequate

infiltration from the outside.

Air Duct Sizing

The air duct requirements shall be met by one of the follow-

ing methods:

1. vertical duct(s) with a free area of not less than 5.5

cm

2

/kWh (1 in

2

/4000 Btu/h) of the total input rating of all

appliances in the enclosure;

2. horizontal duct(s), with an equivalent length of less than

15 m (50 ft), having a free area of not less than 11
cm

2

/kWh (1 in

2

/2000 Btu/h) of the total input of all appli-

ances in the enclosure; and

3. air openings that communicate directly with the outdoors,

having a free area of not less than 5.5 cm

2

/kWh (1

in

2

/4000 Btu/h) of the total input rating of all appliances

in the enclosure.

NOTE: Duct runs that are primarily horizontal and that have

an equivalent length greater than 15 m (50 ft) should be

sized accordingly larger to provide the same air flow as

would be provided by the requirements of method (3) above.

In USA:
Refer to “Standard for the Installation of Oil-Burning

Equipment (NFPA 31)”

Vent and Exhaust Connections
General chimney requirements

For a burner designed for natural draft connect the vent to a

vertical chimney. Insufficient draft can cause flue gas leak-

age and carbon monoxide emissions, which can lead to

severe bodily injury or death. Use vent material approved by

local codes for oil-fired burners. In the absence of such

codes, refer to:

“Installation Code for Oil-Burning Equipment (CSA

B139-04)” (Canadian installations).

“Standard for the Installation of Oil-Burning

Equipment (NFPA 31)” (USA).

“Standard for Chimneys, Fireplaces, Vents, and

Solid Fuel-Burning Appliances (NFPA 211)” (USA).

NFPA 211 requires the chimney to be lined before connect-

ing the oil-fired water heater. Inspect existing chimney

before installing the water heater. Failure to do any of the fol-

lowing can result in serious property damage, severe bodily

injury or death:

• Clean the chimney, including removal of blockage.

• Repair or replace damaged pipe or liner.

• Repair mortar and joints.

To prevent downdrafts, extend the chimney at least 1m (3 ft.)

above highest point where it passes through roof and

610mm (24 in.) higher than any portion of building within 3m

(10 ft.). Increase chimney cross-sectional area and height at

least 4% per 305m (1,000 ft.) above sea level.

Flue Pipe

NOTE: Type “L” vent material is generally considered to be

not suitable for this application. Flue temperatures may

exceed 300°C (572°F). Use flue piping approved for this

installation.

Long horizontal flue pipes, excessive number of tees and

elbows or other obstructions restrict flue gas flow, and can

result in the possibility of condensation, flue gas leakage

and carbon monoxide emissions. These conditions can lead

to serious property damage, severe bodily injury or death.

The flue pipe should be the same size as the breech con-

nection on the appliance. The sizes generally are 150mm (6

in.) for burners rated less than 1.00 GPH and 178mm (7 in.)

for burners rated for 1.00 to 1.50 GPH. The flue pipe should

be as short as possible and installed so that it has a contin-

uous rise of 20mm/m (1/4 in./ft.) of horizontal length from the

breech connection on the appliance to the chimney. Elbows

should be minimized and the sections of pipe and fittings

should be joined with sheet metal screws and straps.

Routing should be made in such a way as to avoid sharp

turns or unduly long runs. It is recommended that the heater

be piped to its own individual flue. Where there is only one

flue for both furnace and water heater, various methods are

practiced in which the water heater flue enters the chimney

above the main smoke pipe. Also, a “Y” fitting is frequently

used in combining both the heater and furnace flues, prior to

entering the chimney connection (see Figure 4, check with

local authorities having jurisdiction). Obtain a gas-tight seal

to prevent possible flue gas leakage and carbon monoxide

emissions, which can lead to severe bodily injury or death.

Draft Regulator

This device is used on conventional chimney venting only. It

automatically maintains a constant negative pressure in the

chimney to obtain maximum efficiency. If the chimney does

not develop sufficient draft, the draft control cannot function

properly. The heater must be equipped with an approved

draft regulator of adequate size. Make sure that the draft

regulator diameter is at least as large as the flue pipe diam-

eter. Follow manufacturers recommended instructions for

installation. It must be installed in the flue pipe before it

enters the chimney and after the Blocked Vent Safety

Switch, if one is used. Set the draft regulator at -0.03 in. (-

0.762mm) of water column, as measured in the flue

(between the heater and the draft regulator). Recommended

over-fire draft is -0.02 in. (-0.5078mm) of water column.

This manual is related to the following products: