¥ Chime option for other partition during 2-way voice session.
¥ VIM text option for displaying voice mode text at the keypad.
¥ VIM AC loss option, when enabled, allows 2-way voice communication after AC

loss (recommended for installations where someone is on a life support device)

¥ The AUTO CALLBACK option, when enabled, allows callback to initiate 2-way

voice communication, otherwise Òlisten in to followÓ (event code 606) is sent at
end of alarm report.

Programming

Information For the

6139AV Keypad

¥ Device address as programmed at the keypad (01-15). Address 00 not

applicable. NOTE: Address 04 is reserved for the 4285 phone module.

¥ Device type "8".
¥ Voice keypad number (01Ð16); this is the keypad's identification number from

the central station operator's point of view. 01Ð06 is recommended.

¥ Keypad's partition (1Ð2).
¥ Keypad's sounder option (0Ð2)

Program VIM fault and siren silencing options by using the #93 Menu Mode -
Relay Programming menu (see Section 4 in the

PART 2. PROGRAMMING GUIDE

section of this manual).

AAV Notes

1. The 685 Receiver software must be rev. 4.6 or higher. Earlier versions will not

hold the phone line connection, or if AUTO CALLBACK is enabled, any
receiver can be used.

2. Contact ID code for "listen-in to follow" is "606" if AUTO CALLBACK is

disabled.

3. Field 1*60 must be set for "0" when using the Ademco VIM module. If using

another manufacturerÕs AAV module, enter Т1У.

N O T E : If set to Т1У, zone 5 is no longer available as a

protection zone.

4. Contact ID (field *45 =1) is the only reporting format that will send a "listen-in

to follow" message if AUTO CALLBACK is disabled.

5. Listen-in to follow message is sent only if both the VIM and at least one

6139AV 2-way voice keypad is programmed using #93 Device Programming
mode if AUTO CALLBACK is disabled.

6. Operator callback and AUTO CALLBACK option is enabled if a non- leading-

zero 4-digit number is programmed in field 1*59.

7. Make sure that field *44 (RING DETECTION COUNT) is not set to Т01У.

6139AV Keypad Audio

Level Adjustment

The 6139AVÕs audio level for "talk mode" and "VOX mode" can be programmed
for "high," "medium," or "low." The factory default is "high."

1. Enter the keypad's programming mode by pressing and holding down the [1]

and [3] keys at the same time for 3 seconds. The keypad's address is
displayed.

2. a. Press and hold down the "D" key for 2 seconds. The current talk mode

audio level is displayed (high, medium, or low).

b. Press the [#] key repeatedly to toggle the talk mode level settings from

high to medium to low until the desired level is displayed.

3. a. Press the "D" key again to enter VOX mode level setting. The current

VOX mode audio level is displayed (high, medium, or low).

b. Press the [#] key repeatedly to toggle the VOX mode level settings from

high to medium to low until the desired level is displayed.

4. Pressing the "D" key again returns to the talk mode level setting, etc.

Press [*] to exit keypad programming mode.

N o t e s :
¥ The keypad returns to normal mode if no key is pressed for 30 seconds.

¥ Powering down the keypad does not change the level setting.

¥ To eliminate undesired keypad feedback (microphonics) during a 2-way audio

session, reduce the VOX mode audio level one level at a time until the
feedback stops.