Xpanded, Eating, Cont – Goodman Mfg GPH13M User Manual
Page 30: Roduct, Pecifications

P
roduct
S
PecificationS
P
roduct
S
PecificationS
30 www.goodmanmfg.com
SS-GPH13M
e
xpAnded
h
eAting
d
AtA
(
Cont
.)
GPH1336M41A*
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
43.0
40.7
38.3
35.8
34.2
33.1
30.8
28.4
24.4
22.6
20.8
19.6
18.9
17.0
15.0
13.1
11.2
9.2
T/R
34.6
32.8
30.8
28.8
27.5
26.7
24.8
22.9
19.7
18.2
16.7
15.8
15.2
13.6
12.1
10.6
9.0
7.4
kW
3.10
3.04
2.98
2.92
2.89
2.86
2.81
2.75
2.36
2.31
2.26
2.24
2.22
2.17
2.12
2.07
2.02
1.97
Amps
15.4
14.4
13.6
12.9
12.5
12.3
11.7
11.1
10.7
10.3
9.9
9.7
9.6
9.2
8.7
8.3
7.8
7.2
COP
4.06
3.92
3.76
3.58
3.46
3.39
3.21
3.02
3.03
2.86
2.69
2.57
2.50
2.29
2.08
1.85
1.62
1.36
EER
13.9
13.4
12.8
12.2
11.8
11.6
11.0
10.3
10.4
9.8
9.2
8.8
8.5
7.8
7.1
6.3
5.5
4.6
Hi Pr
403
386
371
355
347
340
327
314
300
287
276
269
264
254
244
234
226
218
Lo Pr
137
127
119
109
103
99
91
81
73
66
58
54
52
44
38
32
28
22
GPH1336M41C*
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
44.5
42.1
39.7
37.1
35.4
34.3
31.9
29.4
23.7
21.9
20.2
19.0
18.3
16.5
14.6
12.7
10.9
8.9
T/R
34.0
32.2
30.3
28.3
27.0
26.2
24.3
22.4
18.1
16.7
15.4
14.5
14.0
12.6
11.1
9.7
8.3
6.8
KW
3.08
3.02
2.95
2.89
2.86
2.83
2.77
2.71
2.60
2.54
2.48
2.44
2.42
2.35
2.29
2.23
2.17
2.11
AMPS
15.2
14.2
13.4
12.6
12.2
12.0
11.4
10.9
10.5
10.1
9.6
9.4
9.3
8.9
8.4
8.0
7.5
6.8
COP
4.23
4.09
3.93
3.75
3.63
3.55
3.37
3.18
2.67
2.53
2.38
2.28
2.22
2.05
1.86
1.67
1.46
1.23
EER
14.5
14.0
13.4
12.8
12.4
12.1
11.5
10.9
9.1
8.6
8.1
7.8
7.6
7.0
6.4
5.7
5.0
4.2
HI PR
412
395
380
363
355
348
334
321
307
294
282
275
270
260
250
240
231
223
LO PR
138
128
120
110
104
100
92
82
74
66
58
54
52
44
38
32
28
22
GPH1342M41A*
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
50.3
47.6
44.8
41.9
40.0
38.8
36.0
33.2
27.5
25.4
23.4
22.1
21.3
19.1
16.9
14.8
12.6
10.3
T/R
35.8
33.9
31.9
29.8
28.5
27.6
25.6
23.6
19.6
18.1
16.7
15.7
15.1
13.6
12.0
10.5
9.0
7.3
kW
3.58
3.52
3.45
3.38
3.34
3.31
3.25
3.18
2.31
2.27
2.23
2.20
2.18
2.14
2.09
2.05
2.01
1.96
Amps
17.6
16.5
15.6
14.8
14.3
14.1
13.4
12.8
12.3
11.9
11.4
11.2
11.1
10.6
10.0
9.6
9.0
8.3
COP
4.11
3.96
3.80
3.62
3.50
3.42
3.24
3.05
3.48
3.27
3.07
2.94
2.85
2.61
2.36
2.11
1.84
1.54
EER
14.0
13.5
13.0
12.4
12.0
11.7
11.1
10.4
11.9
11.2
10.5
10.0
9.7
8.9
8.1
7.2
6.3
5.3
Hi Pr
323
310
298
285
278
273
262
252
241
230
221
216
212
204
196
188
181
175
Lo Pr
141
131
122
112
106
102
94
84
75
67
59
55
53
45
39
33
29
22
GPH1342M41C*
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
54.8
51.9
48.8
45.6
43.6
42.2
39.2
36.2
30.5
28.1
25.9
24.5
23.6
21.1
18.7
16.3
13.9
11.4
T/R
36.6
34.6
32.6
30.5
29.1
28.2
26.2
24.2
20.4
18.8
17.3
16.3
15.7
14.1
12.5
10.9
9.3
7.6
KW
3.89
3.82
3.74
3.66
3.62
3.59
3.52
3.44
3.21
3.14
3.07
3.03
3.00
2.93
2.86
2.79
2.71
2.64
AMPS
19.5
18.2
17.2
16.3
15.8
15.5
14.7
14.1
13.5
13.0
12.5
12.2
12.1
11.6
10.9
10.4
9.8
9.0
COP
4.12
3.98
3.82
3.64
3.52
3.44
3.26
3.08
2.78
2.63
2.47
2.37
2.30
2.11
1.92
1.72
1.50
1.26
EER
14.1
13.6
13.0
12.5
12.0
11.8
11.2
10.5
9.5
9.0
8.4
8.1
7.9
7.2
6.6
5.9
5.1
4.3
HI PR
434
416
400
383
374
366
352
338
324
309
297
290
285
274
263
253
244
235
LO PR
140
130
122
112
106
101
93
83
75
67
59
55
53
45
39
32
28
22
Above information is for nominal CFM and 70° indoor dry bulb; instantaneous capacity listed.
Amps: Unit amps (comp.+ evap motor + condenser fan motor)
High pressure measured at liquid line access fitting; Low pressure measured at compressor suction access fitting.
kW = Total system power