Expanded heating data, Xpanded, Eating – Goodman Mfg GPH13M User Manual
Page 29: Roduct, Pecifications

P
roduct
S
PecificationS
P
roduct
S
PecificationS
SS-GPH13M
www.goodmanmfg.com
29
e
xpAnded
h
eAting
d
AtA
GPH1324M41A*
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
28.9
27.4
25.8
24.1
23.0
22.3
20.7
19.1
16.7
15.4
14.2
13.4
12.9
11.6
10.3
9.0
7.6
6.3
T/R
32.4
30.7
28.9
27.0
25.8
25.0
23.2
21.4
18.8
17.3
15.9
15.1
14.5
13.0
11.5
10.1
8.6
7.0
kW
2.14
2.10
2.06
2.01
1.99
1.97
1.94
1.89
2.32
2.26
2.21
2.18
2.16
2.10
2.05
2.00
1.95
1.89
Amps
10.4
9.8
9.2
8.8
8.5
8.4
8.0
7.7
7.4
7.1
6.9
6.7
6.7
6.4
6.1
5.8
5.5
5.1
COP
3.96
3.82
3.67
3.50
3.38
3.30
3.13
2.95
2.11
1.99
1.88
1.80
1.75
1.61
1.47
1.31
1.15
0.97
EER
13.5
13.1
12.5
12.0
11.5
11.3
10.7
10.1
7.2
6.8
6.4
6.2
6.0
5.5
5.0
4.5
3.9
3.3
Hi Pr
379
364
350
334
326
320
308
295
283
270
260
253
249
239
230
221
213
205
Lo Pr
135
126
118
108
102
98
90
80
73
65
57
53
51
43
37
31
27
22
GPH1324M41C*
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
31.3
29.6
27.8
26.0
24.9
24.1
22.4
20.6
17.2
15.9
14.6
13.8
13.3
11.9
10.6
9.2
7.9
6.5
T/R
32.6
30.9
29.1
27.2
26.0
25.2
23.4
21.5
18.0
16.6
15.3
14.4
13.9
12.5
11.1
9.6
8.2
6.7
kW
2.11
2.07
2.03
1.99
1.97
1.95
1.92
1.88
1.93
1.89
1.85
1.82
1.81
1.77
1.73
1.69
1.65
1.61
Amps
10.4
9.8
9.3
8.8
8.5
8.4
8.0
7.7
7.4
7.2
6.9
6.8
6.7
6.5
6.1
5.9
5.6
5.2
COP
4.34
4.19
4.01
3.82
3.69
3.61
3.42
3.22
2.61
2.46
2.32
2.22
2.15
1.98
1.79
1.60
1.40
1.18
EER
14.8
14.3
13.7
13.1
12.6
12.3
11.7
11.0
8.9
8.4
7.9
7.6
7.4
6.8
6.1
5.5
4.8
4.0
Hi Pr
377
361
347
332
324
318
306
293
281
268
258
252
247
238
229
219
211
204
Lo Pr
146
135
127
116
110
106
97
87
78
70
61
57
55
46
40
34
30
23
GPH1330M41A*
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
36.2
34.3
32.3
30.2
28.8
27.9
25.9
23.9
21.2
19.6
18.0
17.0
16.4
14.7
13.0
11.4
9.7
7.9
T/R
31.9
30.2
28.4
26.6
25.4
24.6
22.9
21.1
18.7
17.3
15.9
15.0
14.4
13.0
11.5
10.0
8.6
7.0
kW
2.74
2.68
2.63
2.58
2.55
2.53
2.48
2.43
2.29
2.24
2.19
2.17
2.15
2.10
2.05
2.00
1.95
1.90
Amps
13.6
12.7
12.0
11.4
11.1
10.9
10.4
9.9
9.6
9.2
8.9
8.7
8.6
8.2
7.8
7.5
7.0
6.5
COP
3.87
3.74
3.59
3.42
3.30
3.23
3.06
2.88
2.71
2.55
2.40
2.30
2.23
2.05
1.86
1.66
1.46
1.22
EER
13.2
12.8
12.3
11.7
11.3
11.0
10.5
9.8
9.2
8.7
8.2
7.9
7.6
7.0
6.4
5.7
5.0
4.2
Hi Pr
375
359
346
330
323
316
304
292
280
267
256
250
246
236
227
218
210
203
Lo Pr
131
122
114
105
99
95
88
78
70
63
55
51
49
42
36
30
27
21
GPH1330M41C*
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
34.1
32.2
30.3
28.4
27.1
26.2
24.4
22.5
19.9
18.4
16.9
16.0
15.4
13.8
12.2
10.7
9.1
7.5
T/R
28.8
27.3
25.7
24.0
22.9
22.2
20.7
19.0
16.9
15.6
14.3
13.5
13.0
11.7
10.4
9.0
7.7
6.3
KW
2.38
2.34
2.29
2.25
2.22
2.21
2.16
2.12
2.21
2.16
2.12
2.09
2.07
2.02
1.98
1.93
1.89
1.84
AMPS
11.9
11.1
10.6
10.0
9.8
9.6
9.2
8.8
8.5
8.2
7.9
7.8
7.7
7.4
7.1
6.8
6.4
6.0
COP
4.19
4.04
3.87
3.69
3.56
3.48
3.30
3.10
2.64
2.49
2.34
2.24
2.18
2.00
1.81
1.62
1.41
1.19
EER
14.3
13.8
13.2
12.6
12.2
11.9
11.3
10.6
9.0
8.5
8.0
7.7
7.4
6.8
6.2
5.5
4.8
4.1
HI PR
355
341
328
313
306
300
288
277
265
253
243
237
233
224
216
207
199
192
LO PR
133
124
116
106
100
97
89
79
71
64
56
52
50
42
37
31
27
21
Above information is for nominal CFM and 70° indoor dry bulb; instantaneous capacity listed.
Amps: Unit amps (comp.+ evap motor + condenser fan motor)
High pressure measured at liquid line access fitting; Low pressure measured at compressor suction access fitting.
kW = Total system power