Cpg060, Irflow, Cont – Goodman Mfg SS-CPG36-72 User Manual
Page 28

28
www.goodmanmfg.com
SS-CPG36-72
SS-CPG36-72
www.goodmanmfg.com
29
P
roduct
S
PecificationS
P
roduct
S
PecificationS
a
irFlow
d
ata
— CPG060 (
Cont
.)
s
tandard
B
elt
d
rive
— h
orizontal
ESP
(“ H
2
O)
Turns Open
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
---
---
---
---
2460
0.96
2251
0.80
2073
0.65
1862
0.51
0.4
---
---
2408
1.00
2206
0.84
1982
0.68
1808
0.55
1572
0.41
0.6
2402
1.08
2173
0.89
1943
0.72
1701
0.55
1511
0.43
---
---
0.8
2153
0.95
1917
0.77
1667
0.59
---
---
---
---
---
---
1.0
1888
0.82
1634
0.63
---
---
---
---
---
---
---
---
1.2
1601
0.67
---
---
---
---
---
---
---
---
---
---
h
iGh
-s
tatiC
B
elt
d
rive
— h
orizontal
ESP
(“ H
2
O)
Turns Open
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.6
---
---
---
---
---
---
---
---
2219
0.95
1970
0.75
0.8
---
---
---
---
---
---
2215
1.04
1956
0.82
1697
0.62
1.0
---
---
---
---
2240
1.15
1957
0.90
1681
0.67
---
---
1.2
---
---
2260
1.26
1983
1.00
1683
0.74
---
---
---
---
1.4
2288
1.38
2009
1.10
1711
0.84
---
---
---
---
---
---
1.6
2032
1.21
1741
0.93
---
---
---
---
---
---
---
---
1.8
1776
1.04
---
---
---
---
---
---
---
---
---
---
s
tandard
B
elt
d
rive
— d
own
s
hot
ESP
(“ H
2
O)
Turns Open
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
---
---
2210
0.91
2041
0.76
1869
0.63
1739
0.52
1565
0.40
0.4
2197
0.98
2021
0.82
1841
0.67
1660
0.54
1521
0.44
1339
0.32
0.6
2002
0.88
1822
0.72
1635
0.58
1445
0.44
1288
0.35
---
---
0.8
1799
0.77
1610
0.62
1425
0.48
---
---
---
---
---
---
1.0
1587
0.67
1384
0.51
---
---
---
---
---
---
---
---
h
iGh
-s
tatiC
B
elt
d
rive
— d
own
s
hot
ESP
(“ H
2
O)
Turns Open
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.6
---
---
---
---
2262
1.16
2051
0.95
1851
0.76
1657
0.60
0.8
---
---
2277
1.27
2070
1.05
1852
0.84
1646
0.66
---
---
1.0
2304
1.39
2089
1.15
1872
0.93
1647
0.72
---
---
---
---
1.2
2104
1.26
1893
1.03
1668
0.81
---
---
---
---
---
---
1.4
1912
1.13
1690
0.90
---
---
---
---
---
---
---
---
1.6
1720
1.00
---
---
---
---
---
---
---
---
---
---
Note: Tables represent dry coil without filter; to compensate for filter, add 0.08” to measured E.S.P. SCFM correction for wet coil = 4%.