Epm 5000 series advanced power meters ge multilin – GE EPM 5200 User Manual
Page 72

CHAPTER 11: PROGRAMMING GROUP 2 – METER CALIBRATION
68
EPM 5000 series Advanced Power Meters GE Multilin
VOLTAGE RANGE
INPUT SOURCE
GROUP 2 VALUE
69.3/120V 75V 1440
120/208V 120V
L-N 1440
277/480V 300V 0300
5A CT High End
5A
2000
2.5A Low End
2.5A
1000
Table 11-2: Calibration Source, Full Scale and Value Settings for Calibration
11.2: Group 2, Functions 0–2—High End Calibration of Voltage Channels, High
and Low End Calibration of Amperage Channels
To change the calibration (high end—Functions 0 and 1):
NOTE: Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
Step 1:
a. Enter Group Level of Programming Mode
(see Chp. 8).
b. Press MAX/MIN/LIMITS until 2. appears in
upper display.
c. Press AMPS to activate the Group.
!
A one-digit password is required to continue.
d. Press VOLTS until 5 appears.
e. Press AMPS to select.
Step 2:
!
Refer to Table 11-1 for Function Number that
corresponds to the area requiring calibration. Calibration
for each area begins with A and then moves to B and C.
a. Press MAX/MIN/LIMITS to change Function number.