Group 0: global meter setup, Function 0: the integration interval, Chapter 9 programming group 0 – global meter setup – GE EPM 5200 User Manual
Page 47: Group 0, function 0—the integration interval, Ge industrial systems 5300p advanced power meter, Table 9-1 : group 0 programming format

CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP
GE Industrial Systems 5300P Advanced Power Meter
43
CHAPTER 9
PROGRAMMING GROUP 0 – GLOBAL METER SETUP
The Global Meter Setup includes FUNCTIONS 0 through 7 that control configuration and basic operation.
FUNCTION 3 System Configuration contains Switch PACKS with various options, including Open Delta
installation, communications or DC Output setup. Global Meter Setup is the section in which general
features are programmed.
FUNCTION
NUMBER
Function
0. Integration
Interval
1.
Meter Address for Communication
2.
Baud Rate for Communication
3.
System Configuration (see Table 9-2)
4.
Relay 1 Set-up / Time delay
5.
Relay 2 Set-up / Time delay
6.
KYZ Parameter Selection
7.
Number of Phases
E.
Exit Programming GROUP 0
Table 9-1: Group 0 Programming Format
9.1: Group 0, Function 0—The Integration Interval
INTEGRATION INTERVAL: Time which all instantaneous readings are averaged to obtain a max and
min demand. The Integration Interval is entered in seconds. When entering 15 minutes, enter: 0900
seconds. The default value is 900 seconds.
To change the Integration Interval:
NOTE: Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
Step 1:
a. Enter Group Level of Programming Mode
(see Chp. 8).
b. Press MAX/MIN/LIMITS until 0. appears in upper
display.
c. Press AMPS to activate the Group.
!
Function 00. appears in upper display. The second 0
indicates Function 0
!