Troubleshooting, Blower does not operate – Greenheck Fan Make-Up Air Unit VSU User Manual

Page 14

background image

14

Model VSU Make-Up Air

®

®

®

®

®

115 VAC between

terminals 102 and 101?

Check Main Voltage

(See Blower Start-Up Step #1)

Main Disconnect (DS1) Off

(Turn Main Disconnect DS1 On)

Primary Fuses Blown

(Replace Fuses)

Main Transformer Defective

(Replace Transformer)

24 VAC between

terminals R and X?

Main Transformer Defective

(Replace Transformer)

24 VAC between

terminals G and X?

Supply Switch (S2) Off

(Turn Supply Switch (S2) On)

No

No

No

No

Yes

Yes

Yes

Yes

Blower Does Not Operate

Broken Fan Belt

(Replace - Reference Maintenance section)

Defective motor or capacitor

(Repair/Replace)

Blown Motor Fuse

(Replace)

One or more legs of 3 phase is out

(Restore missing legs)

24 VAC between

terminals 7 and X?

Damper Limit Switch (DL1) Holding

(Wait for actuator to open fully or adjust limit switch)

Troubleshooting

At this time the supply should be energized., passing

power to the supply motor and the blower should start.